| Plan Review Notes For Permit 15040753 |
| Permit Number |
15040753 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-04 10:01:08 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) INDICATE THE LOCATION OF THE SOURCE FOR THE CABLE | | | RUN. THE PLAN INDICATES ONLY THE ROOM WHERE THE CABLE | | | TERMINATES. | | | | | | 2) ALWAYS PROVIDE THE MANUFACTURER INFORMATION FOR THE | | | EQUIPMENT AND CABLES TO BE INSTALLED OR AT MINIMUM | | | INDICATE THE CABLE TYPE TO BE INSTALLED. | | | | | | 3) SIGN ALL PLANS. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. FBC, WPB AMENDMENTS 107.2.1 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|