| Plan Review Notes For Permit 15040738 |
| Permit Number |
15040738 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-06-30 13:37:27 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING | | | REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- A) MISSING DRAWINGS. MISSING DRAWINGS A-2, S-1 AND | | | S-2.. | | | | | | B) ONE SET OF SHEET S-2 AND S-3 SUBMITTED IS MISSING | | | THE ENGINEER'S SEAL. SEC. 471 F.S. | | | | | | 2- ENERGY CALCULATIONS SUBMITTED; | | | A) REVISE THE WINDOWS OVERHANG DEPTH AND SEPARATION TO | | | MATCH PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY | | | CONSERVATION. (REPEAT COMMENT). | | | | | | B) REVISE DOOR TYPE TO MATCH PRODUCT APPROVAL AND | | | PLANS. NOTE: DOORS WITH GLAZING SHALL BE INCLUDED IN | | | THE GLAZING CALCULATIONS. SEE SEC. 405.5.3 OF 2010 | | | FBC-ENERGY CONSERVATION. (REPEAT COMMENT. THERE ARE NO | | | INSULATED DOORS). | | | | | | C) COMPLETE PAGE 5 OF 5. SEC. 103.2.2 OF 2010 | | | FBC-ENERGY CONSERVATION. (REPEAT COMMENT). | | | | | | ***IMPORTANT: WINDOWS AND DOORS LABELS SHOWING THE | | | U-FACTORS AND SHGC FACTORS SPECIFIED ON ITEM #7 ARE | | | REQUIRED FOR INSPECTION. | | | | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR: | | | A) ROOF TILE ADHESIVE AS SPECIFIED ON SHEET S-4. SEE | | | ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 |
|