Plan Review Notes
Plan Review Notes For Permit 15040738
Permit Number 15040738
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-27 11:00:441ST REVIEW: FBC 2010 MECHANICAL
  
 1) THE AC PLANS FROM CMI SHOW THE AIR HANDLER IN THE
 BONUS ROOM ADDITION, HOWEVER THE ELECTRICAL PLANS SHOWS
 IT IN THE ATTIC: PLEASE MAKE THESE PLANS AGREE ON
 LOCATION. SEE SECTION M1305.1.3.2FBC-RESIDENTIAL FOR
 AIR HANDLER IN ATTIC REQUIREMENTS.
 2) SUBMIT MANUAL J AC LOAD WORKSHEETS INDICATING THE
 CALCULATIONS PER EACH ROOM OF THE NEW ADDITION. THE
 SUBMITTED SUMMARY CALC SHEET DOES NOT INDICATE THE
 ADDRESS, DIRECTIONAL ORIENTATION OR AREA CALCULATION-
 SECTION 403.6.1 FBC-10 ENERGY.
 3) THE AC PLAN DOESN'T INDICATE A MEANS OF RETURN AIR
 FROM THE BONUS ROOM- SECTION M1602.4 FBC-10
 RESIDENTIAL.
 4) PROVIDE A PRIMARY CONDENSATE DISPOSAL PLAN- SHOW
 TYPE AND SIZE OF PIPING, PIPING RUN, AND DISCHARGE
 LOCATION. PLACE A NOTE OR DETAIL CLARIFYING HOW
 SECONDARY DISPOSAL WILL BE ACCOMPLISHED- SECTION
 M1411.3 FBC-10 RES.
 5) SHOW THE REFRIGERATION PIPING RUNS ON THE PLAN.
 6) PROVIDE DETAILS FOR INSTALLATION OF THE CONDENSER
 PAD AND TIE DOWN OF THE UNIT PER SECTIONS- M1305.1.4.1
 AND M1307.2.1 FBC-10 RES.
 7) ENERGY EFFICIENCY FORM 405-2010: COMPLETE THE CODE
 COMPLIANCE CHECKLIST ON PAGE 5.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  