| Notes |
| Date |
Text |
| 2015-05-14 17:58:30 | DISPOSITION AND RESPECTIVE COMMENTS FOR ELECTRICAL PLAN | | | REVIEW | | | APPLICABLE CODES: FBC 2010; WPB AMENDMENTS TO FBC 2010 | | | CHAPTER 1; NEC 2008 | | | REVIEW CYCLE: 1ST REVIEW | | | ACTION: FAILED AS NOTED BELOW: | | | 1. INDICATE THE SCALE USED FOR THE DRAWING TO PROPERLY | | | ASCERTAIN OUTLET PLACEMENT. ALL OUTLETS SHALL BE AS PER | | | NEC 210.52 | | | 2. PER NEC 110.33(B), A PERMANENT LADDER OR STAIRWAY TO | | | THE ATTIC WILL BE REQUIRED TO ACCESS THE AHU. | | | 3. PER NEC 210.63, A SERVICE OUTLET SHALL BE INSTALLED | | | IN THE ATTIC WITHIN SIGHT AND NO MORE THAN 25' FROM THE | | | AHU | | | 4. PER NEC 210.70(A)(3), A LIGHT WITH A SWITCH AT THE | | | ENTRY TO THE ATTIC SHALL BE INSTALLED INSIDE THE ATTIC | | | NEAR THE AHU | | | 5. PER NEC 210.52(E)(3), AN OUTLET SHALL BE INSTALLED | | | IN THE BALCONY | | | 6. PER NEC 314.27(A), CEILING BOXES SHALL BE LISTED TO | | | SUPPORT 50#. | | | 7. PER FBC-R SEC. 314 & 315, ADDITIONAL DETECTORS MAY | | | BE REQUIRED. | | | |
|