| 2015-05-26 15:10:20 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| | FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| | PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY |
| | IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT |
| | CODE. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED; |
| | A) WALL TYPES IS MISSING THE FRAMED WALLS OF THE BONUS |
| | ROOM. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | B) REVISE THE BUILDING ORIENTATION OF WALLS, DOORS AND |
| | WINDOWS TO MATCH THE ACTUAL BUILDING ORIENTATION OF THE |
| | EXISTING HOUSE. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH |
| | PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | D) REVISE DOOR TYPE TO MATCH PRODUCT APPROVAL AND |
| | PLANS. NOTE: DOORS WITH GLAZING SHALL BE INCLUDED IN |
| | THE GLAZING CALCULATIONS. SEE SEC. 405.5.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | E) COMPLETE PAGE 5 OF 5. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | F) COMPLETE ALL THE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER, BUILDER NAME, PERMIT OFFICE AND THE |
| | JURISDICTION NUMBER. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 3- SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. REQUIRES 8D |
| | RING SHANK NAILS MIN. FOR ROOF SHEATHING. PLANS CALL |
| | FOR "ALT: 8D .131 DIA. W/ TYP. NAILING PATTERN". |
| | PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE |
| | ALTERNATIVE NAILS AND NAILING PATTERN ARE EQUAL OR |
| | BETTER THAN THE MIN. REQUIRED BY SEC. R803.2.3.1. (SEC. |
| | 107.2.1.3 CITY AMENDMENTS). REVISE GENERAL CONSTRUCTION |
| | NOTES ON SHEET A-1, ROOF FRAMING NOTES ON SHEET S-3 AND |
| | ALL WALL SECTIONS ON SHEET S-4. |
| | |
| | 4- SHEET S-4: |
| | A) ATTIC INSULATION SHOWN ON THE WALL SECTIONS TO MATCH |
| | ENERGY CALCULATIONS. OPTIONAL R19 IS NOT INCLUDED IN |
| | THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | B) FRAMED WALL REQUIRES 7/8" MIN. STUCCO NOT 3/4". |
| | TABLE R702.1(1) OF 2010 FBC-RESIDENTIAL. |
| | |
| | C) ROOF SHEATHING SPECIFICATIONS SHOWN ON GABLE END |
| | DETAIL 4/S-4 DOESN'T MATCH ROOF SHEATHING SPECS SHOWN |
| | ON THE OTHER SECTIONS. REVISE AS REQUIRED. SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF TILE. |
| | |
| | B) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL |
| | FOR LISTED ADHESIVES. |
| | |
| | C) PROVIDE LEGIBLE DRAWINGS FOR PRODUCT APPROVAL |
| | SUBMITTED FOR SERIES "130 SENTINEL" FIXED WINDOWS, |
| | SERIES "238 DESIGNER" FIXED WINDOWS, WINDOW MULLIONS, |
| | SERIES "160 SENTINEL" OUTSWING DOORS AND SERIES "110 |
| | SENTINEL" SINGLE HUNG WINDOWS. DRAWINGS ARE TOO SMALL. |
| | SEC. 107.2.1.4 CITY AMENDMENTS. PLEASE PRINT DRAWINGS |
| | IN LANDSCAPE FORMAT INSTEAD OF PORTRAIT FORMAT. THIS |
| | WAY DRAWINGS WILL BE MORE LEGIBLE. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET. |
| | |