2015-05-26 15:10:20RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  
 2- ENERGY CALCULATIONS SUBMITTED;
 A) WALL TYPES IS MISSING THE FRAMED WALLS OF THE BONUS
 ROOM. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE THE BUILDING ORIENTATION OF WALLS, DOORS AND
 WINDOWS TO MATCH THE ACTUAL BUILDING ORIENTATION OF THE
 EXISTING HOUSE. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 C) REVISE THE WINDOWS OVERHANG SEPARATION TO MATCH
 PLANS. SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 D) REVISE DOOR TYPE TO MATCH PRODUCT APPROVAL AND
 PLANS. NOTE: DOORS WITH GLAZING SHALL BE INCLUDED IN
 THE GLAZING CALCULATIONS. SEE SEC. 405.5.3 OF 2010
 FBC-ENERGY CONSERVATION.
  
 E) COMPLETE PAGE 5 OF 5. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 F) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER, BUILDER NAME, PERMIT OFFICE AND THE
 JURISDICTION NUMBER. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 3- SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. REQUIRES 8D
 RING SHANK NAILS MIN. FOR ROOF SHEATHING. PLANS CALL
 FOR "ALT: 8D .131 DIA. W/ TYP. NAILING PATTERN".
 PROVIDE ENGINEERING CALCULATIONS SHOWING THAT THE
 ALTERNATIVE NAILS AND NAILING PATTERN ARE EQUAL OR
 BETTER THAN THE MIN. REQUIRED BY SEC. R803.2.3.1. (SEC.
 107.2.1.3 CITY AMENDMENTS). REVISE GENERAL CONSTRUCTION
 NOTES ON SHEET A-1, ROOF FRAMING NOTES ON SHEET S-3 AND
 ALL WALL SECTIONS ON SHEET S-4.
  
 4- SHEET S-4:
 A) ATTIC INSULATION SHOWN ON THE WALL SECTIONS TO MATCH
 ENERGY CALCULATIONS. OPTIONAL R19 IS NOT INCLUDED IN
 THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) FRAMED WALL REQUIRES 7/8" MIN. STUCCO NOT 3/4".
 TABLE R702.1(1) OF 2010 FBC-RESIDENTIAL.
  
 C) ROOF SHEATHING SPECIFICATIONS SHOWN ON GABLE END
 DETAIL 4/S-4 DOESN'T MATCH ROOF SHEATHING SPECS SHOWN
 ON THE OTHER SECTIONS. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF TILE.
  
 B) ROOF TILE ADHESIVE. SEE ROOF TILE PRODUCT APPROVAL
 FOR LISTED ADHESIVES.
  
 C) PROVIDE LEGIBLE DRAWINGS FOR PRODUCT APPROVAL
 SUBMITTED FOR SERIES "130 SENTINEL" FIXED WINDOWS,
 SERIES "238 DESIGNER" FIXED WINDOWS, WINDOW MULLIONS,
 SERIES "160 SENTINEL" OUTSWING DOORS AND SERIES "110
 SENTINEL" SINGLE HUNG WINDOWS. DRAWINGS ARE TOO SMALL.
 SEC. 107.2.1.4 CITY AMENDMENTS. PLEASE PRINT DRAWINGS
 IN LANDSCAPE FORMAT INSTEAD OF PORTRAIT FORMAT. THIS
 WAY DRAWINGS WILL BE MORE LEGIBLE.
  
 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET.
  