| 2015-04-22 14:37:16 | 600 OKEECHOBEE BOULEVARD |
| | PERMIT #15040691 |
| | MASTER #14050111 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PERMIT VALUE OF $5,000 APPEARS TO BE UNDERVALUED. |
| | SUBMIT A COPY OF THE OFFICIAL SIGNED CONTRACT. THE |
| | TOTAL PERMIT JOB VALUE NEEDS TO INCLUDE MATERIALS AND |
| | LABOR. |
| | |
| | PROVIDE DETAILED SCALABLE SHOP DRAWINGS. THE PLANS |
| | SUBMITTED ARE ONLY SCHEMATIC IN NATURE. PLANS DO NOT |
| | INDICATE THE FLOOR LEVELSL OR LOCATIONS OF WHERE THESE |
| | HOOD FIRE SUPPRESSION SYSTEMS ARE LOCATED. PER NFPA 96 |
| | SECTION 10.9.1 WHERE REQUIRED, COMPLETE DRAWINGS OF THE |
| | SYSTEM INSTALLATION, INCLUDING THE HOOD(S), EXHAUST |
| | DUCT(S), AND APPLIANCES, |
| | ALONG WITH THE INTERFACE OF THE FIRE-EXTINGUISHING |
| | SYSTEM DETECTORS, PIPING, NOZZLES, FUEL AND ELECTRIC |
| | POWER SHUTOFF DEVICES, AGENT STORAGE CONTAINER(S), AND |
| | MANUAL ACTUATION DEVICE(S), SHALL BE SUBMITTED TO THE |
| | AUTHORITY HAVING JURISDICTION. |
| | |
| | SUBMIT EQUIPMENT CUTSHEETS FOR THE ANSUL R-102 SYSTEMS. |
| | |
| | THE PLANS INDICATE "COMPLIANCE WITH NFPA 96 AND NFPA |
| | 17"; HOWEVER, NO EDITIONS OF THE STANDARDS ARE |
| | INDICATED. |
| | |
| | THE PLANS INDICATE ONLY ELECTRIC UNDER THE HOOD TO BE |
| | SHUTDOWN. UPON ACTIVATION OF ANY FIRE-EXTINGUISHING |
| | SYSTEM FOR A COOKING OPERATION, ALL SOURCES OF FUEL AND |
| | ELECTRICAL POWER THAT PRODUCE HEAT TO ALL EQUIPMENT |
| | REQUIRING PROTECTION BY THAT SYSTEM SHALL AUTOMATICALLY |
| | SHUT OFF. |
| | |
| | HOODS INSTALLED END TO END, BACK TO BACK, OR BOTH, OR |
| | SHARING A COMMON DUCTWORK, AND HAVING A |
| | GREASE-PRODUCING APPLIANCE(S) LOCATED UNDER ONE OR MORE |
| | OF THE HOODS SHALL BE CONSIDERED A SINGLE HAZARD AREA |
| | REQUIRING SIMULTANEOUS AUTOMATIC FIRE PROTECTION IN ALL |
| | HOODS AND DUCTS. |
| | |
| | THE PLANS SHOW MANUAL PULL STATIONS; HOWEVER, THE |
| | LOCATIONS ARE GENERIC. AT LEAST ONE MANUAL ACTUATION |
| | DEVICE SHALL BE LOCATED A MINIMUM OF 10 FEET AND A |
| | MAXIMUM OF 20 FEET FROM THE PROTECTED KITCHEN |
| | APPLIANCE(S) WITHIN THE PATH OF EGRESS. MANUAL |
| | ACTIVATION USING A CABLE-OPERATED PULL STATION SHALL |
| | NOT REQUIRE MORE THAN 178 N (40 LB) OF FORCE, WITH A |
| | PULL MOVEMENT NOT TO EXCEED 14-INCHES TO ACTIVATE THE |
| | AUTOMATIC FIRE-EXTINGUISHING EQUIPMENT. |
| | |
| | A PLACARD SHALL BE CONSPICUOUSLY PLACED NEAR EACH |
| | EXTINGUISHER THAT STATES THAT THE FIRE PROTECTION |
| | SYSTEM SHALL BE ACTIVATED PRIOR TO USING THE FIRE |
| | EXTINGUISHER. INSTRUCTION SHALL BE PROVIDED TO |
| | EMPLOYEES REGARDING THE PROPER USE OF PORTABLE FIRE |
| | EXTINGUISHERS AND THE MANUAL ACTIVATION OF |
| | FIRE-EXTINGUISHING EQUIPMENT. |
| | |