| Plan Review Notes For Permit 15040684 |
| Permit Number |
15040684 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-22 15:18:03 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) PROVIDE ADDITIONAL INFORMATION FROM THE MANUFACTURER | | | THAT STATES THE RETROFIT KIT IS COMPATABLE WITH ALL | | | PANEL TYPES OR AT THE VERY LEAST THE LANEL TYPE YOU ARE | | | REPLACING. | | | | | | 2) PROVIDE A COMPLETE RISER DIAGRAM THAT CLARIFIES THE | | | COMPLETE SCOPE OF WORK AS WELL AS THE WIRE TYPE AND | | | SIZE IN EACH OF THE FEEDER CONDUITS AND NIPPLES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|