Plan Review Notes
Plan Review Notes For Permit 15040684
Permit Number 15040684
Review Stop E
Sequence Number 1
Notes
Date Text
2015-04-22 15:18:03REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE ADDITIONAL INFORMATION FROM THE MANUFACTURER
 THAT STATES THE RETROFIT KIT IS COMPATABLE WITH ALL
 PANEL TYPES OR AT THE VERY LEAST THE LANEL TYPE YOU ARE
 REPLACING.
  
 2) PROVIDE A COMPLETE RISER DIAGRAM THAT CLARIFIES THE
 COMPLETE SCOPE OF WORK AS WELL AS THE WIRE TYPE AND
 SIZE IN EACH OF THE FEEDER CONDUITS AND NIPPLES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved