| Plan Review Notes For Permit 15040671 |
| Permit Number |
15040671 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-05 09:49:38 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLEASE HAVE ENGINEER VERIFY THE CLASSIFICATION OF | | | "C" FOR EXPOSURE CATEGORY. | | | | | | SEE FBC 2010 RESIDENTIAL 301; IT APPEARS THAT THIS | | | STRUCTURE IS LOCATED LESS THAN 600' FROM THE WATER'S | | | EDGE MEASURING TO THE NORTHEAST (OR TO THE SOUTHEAST). | | | ON THIS ANGLE, THERE IS A FETCH OF OVER APPROX. 5200 | | | FEET. IT APPEARS THAT THIS STRUCTURE IS LOCATED IN | | | EXPOSURE D. | | | | | | EITHER CHANGE THE EXPOSURE CLASSIFICATION TO "D", | | | REVISE OTHER DOCUMENTS AS APPLICABLE, OR PROVIDE A SITE | | | PLAN WHICH SHOWS THE WORST CASE MEASUREMENT IN BOTH | | | DIRECTIONS TO JUSTIFY THE ENGINEER'S CLASSIFICATION OF | | | EXPOSURE C. | | | |
|