| 2015-06-25 16:18:57 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | 1. AN ELECTRICAL PERMIT FOR THIS WORK SHALL BE |
| | REQUIRED. |
| | 2. IF THIS WERE A REVISION TO THE MASTER PERMIT |
| | 14050111, YOUR REFERENCES TO THE PAGES THERETO WOULD BE |
| | ACCEPTABLE. THIS IS NOT A REVISION TO THE PERMIT BUT A |
| | SEPARATE PERMIT ALL TOGETHER AND THE REQUIRED |
| | INFORMATION HAS TO ACCOMPANY THE PERMIT SUBMITTAL. |
| | 3. THE ELECTRICAL DIAGRAM OF PAGE 2 OF 3 SHALL BE |
| | AMENDED TO INDICATE THE EXACT PANEL WHERE THIS POOL |
| | PANEL IS BEING SERVED FROM, FURTHERMORE AS INDICATED IN |
| | NEC 230.70 A PLAQUE INDICATING THE LOCATION OF SUCH |
| | DISCONNECT SHALL BE PLACED ON ?PANEL P?. |
| | 4. INDICATE ON THE PLANS THE LOCATION OF THE REQUIRED |
| | EMERGENCY SHUT-OFF SWITCH. |
| | 5. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE NEW |
| | ?WP? PANEL. |
| | 6. THIS IS AN OUTDOOR SPA, THUS AREA LIGHTING IS |
| | REQUIRED. INDICATE POWER SOURCE FOR SUCH LIGHTING & |
| | MAKE SURE IT COMPLIES W/FBC-E ?505. |
| | 7. PROVIDE DOCUMENTATION ON ADA LIFT IF IT HAS ANY |
| | ELECTRICAL COMPONENTS. |
| | 8. AS ONLY SPA ELECTRICAL DATA IS PROVIDED, MODIFY |
| | PERMIT TO REMOVE ?COMMERCIAL POOL? |
| | |
| | ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON |
| | THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER |
| | DIAGRAM AS SHOWN ON E4.01 AS IT DOESN?T PERTAIN TO THIS |
| | PERMIT, BUT YOU DO HAVE TO INCLUDE A RISER DIAGRAM |
| | SHOWING PANEL P AS THE SOURCE OF SERVICE. INDICATE ITS |
| | LOCATION AND ADD THE NOTES INDICATED ABOVE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CONTACT ME. |
| | |
| | RESPECTFULLY SUBMITTED, |
| | |
| | MIKE ALBARRAN |
| | |