Plan Review Notes
Plan Review Notes For Permit 15040663
Permit Number 15040663
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-25 16:18:57PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
  
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. AN ELECTRICAL PERMIT FOR THIS WORK SHALL BE
 REQUIRED.
 2. IF THIS WERE A REVISION TO THE MASTER PERMIT
 14050111, YOUR REFERENCES TO THE PAGES THERETO WOULD BE
 ACCEPTABLE. THIS IS NOT A REVISION TO THE PERMIT BUT A
 SEPARATE PERMIT ALL TOGETHER AND THE REQUIRED
 INFORMATION HAS TO ACCOMPANY THE PERMIT SUBMITTAL.
 3. THE ELECTRICAL DIAGRAM OF PAGE 2 OF 3 SHALL BE
 AMENDED TO INDICATE THE EXACT PANEL WHERE THIS POOL
 PANEL IS BEING SERVED FROM, FURTHERMORE AS INDICATED IN
 NEC 230.70 A PLAQUE INDICATING THE LOCATION OF SUCH
 DISCONNECT SHALL BE PLACED ON ?PANEL P?.
 4. INDICATE ON THE PLANS THE LOCATION OF THE REQUIRED
 EMERGENCY SHUT-OFF SWITCH.
 5. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE NEW
 ?WP? PANEL.
 6. THIS IS AN OUTDOOR SPA, THUS AREA LIGHTING IS
 REQUIRED. INDICATE POWER SOURCE FOR SUCH LIGHTING &
 MAKE SURE IT COMPLIES W/FBC-E ?505.
 7. PROVIDE DOCUMENTATION ON ADA LIFT IF IT HAS ANY
 ELECTRICAL COMPONENTS.
 8. AS ONLY SPA ELECTRICAL DATA IS PROVIDED, MODIFY
 PERMIT TO REMOVE ?COMMERCIAL POOL?
  
 ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON
 THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER
 DIAGRAM AS SHOWN ON E4.01 AS IT DOESN?T PERTAIN TO THIS
 PERMIT, BUT YOU DO HAVE TO INCLUDE A RISER DIAGRAM
 SHOWING PANEL P AS THE SOURCE OF SERVICE. INDICATE ITS
 LOCATION AND ADD THE NOTES INDICATED ABOVE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 RESPECTFULLY SUBMITTED,
  
 MIKE ALBARRAN
  