| 2015-05-02 07:55:00 | 1) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED |
| | WITHIN 200 FEET WALKING DISTANCE OF THE NEAREST WATER'S |
| | EDGE OF EACH POOL SERVED BY THE FACILITIES. 2010 FBC |
| | SEC. 424.1.6. |
| | 2) THE BUILDING PERMIT APPLICATION NOTES THE |
| | DESCRIPTION OF WORK AS "NEW COMMERCIAL POOL AND SPA" |
| | BUT THE PLANS ALSO SHOW PIPING FOR A FOUNTAIN. CLARIFY. |
| | 3) THE WATER FILL FOR THE COLLECTOR TANK SHALL BE |
| | EQUIPPED WITH A REDUCED PRESSURE BACKFLOW PREVENTER PER |
| | CITY ORDINANCE AND THE CITY'S CROSS CONNECTION CONTROL |
| | MANUAL. |
| | 4) SUBMIT MANUFACTURING SPECS FOR THE POOL HEATERS. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 5) PROVIDE CALCULATIONS ON THE PLAN THAT THE MAXIMUM |
| | FILTRATION RATE THROUGH THE CARTRIDGE FILTERS DOES NOT |
| | EXCEED 0.075 PER THE 2010 FBC SEC.424.1.6.5.5.1. |
| | 6) PROVIDE MANUFACTURER'S SPECIFICATION SHEETS FOR THE |
| | TYPE OF LIFT TO BE USED TO PROVIDE HANDICAP |
| | ACCESSIBILITY TO THE SPA. |
| | 7) SUBMIT DOCUMENTATION THAT THE GRATING ON THE SPA |
| | MAIN DRAIN COMPLIES WITH 2010 FBC SEC.424.1.6.5.10.2. |
| | SUBMIT MANUF. SPECIFICATIONS FOR THE MAIN DRAIN COVER. |
| | 8) THE PIPING PLAN SHOWS THE POOL WATER DISCHARGING TO |
| | THE SANITARY SEWER. POOL WATER SHALL NOT DISCHARGE TO |
| | THE SANITARY SEWER PER CITY ORDINANCE 90-126 ( B) (5). |
| | 9)SUBMIT MSDS DOCUMENTS FOR THE THE CHLORINE AND THE |
| | "ACID'.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 10) SUBMIT DETAILS/SPECS FOR THE CHEMICAL FEEDERS.THE |
| | FEEDERS SHALL COMPLY WITH ANSI/NSF 50 - 2007 PER 2010 |
| | FBC SEC.424.1.6.5.16. |
| | 11) THE SPA POOL HEATER SHALL HAVE VALVES PROVIDED |
| | WHICH ALLOW FOR THE ISOLATION OR REMOVAL OF THE HEATER |
| | FROM THE SYSTEM. THE DESIGN DOES NOT APPEAR TO MEET |
| | THIS REQUIREMENT. SEE 2010 FBC SEC.424.1.6.5.14. |
| | |
| | |
| | THIS REVIEW DID NOT INCLUDE THE POOL HOUSE BUILDING FOR |
| | THE MINIMUM SANITARY FACILITY REQUIREMENTS FOR THE |
| | RESTROOMS. |
| | |
| | |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |