| 2015-06-25 18:12:07 | PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS |
| | EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE |
| | MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO |
| | THE CORRECTIONS NOTED. |
| | |
| | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | 1. AN ELECTRICAL PERMIT FOR THIS WORK SHALL BE |
| | REQUIRED. |
| | 2. THE ELECTRICAL DIAGRAM OF PAGE 3 OF 4 SHALL BE |
| | AMENDED TO INDICATE THE EXACT PANEL WHERE THIS POOL |
| | PANEL IS BEING SERVED FROM, FURTHERMORE AS INDICATED IN |
| | NEC 230.70 A PLAQUE INDICATING THE LOCATION OF SUCH |
| | DISCONNECT SHALL BE PLACED ON ?PANEL P?. |
| | 3. PROVIDE PANEL SCHEDULE AND LOAD CALCS FOR THE NEW |
| | ?WP? PANEL. (THIS NEW PANEL IS LABELED ?WP? AS IS FOR |
| | THE SPA. IF THEY ARE ONE AND THE SAME, INDICATE SO |
| | OTHERWISE LABEL THEM DIFFERENTLY. THESE CALCS SHOULD |
| | INDICATE FEEDER CONDUCTOR TYPE & SIZING AS WELL. |
| | 4. THIS IS AN OUTDOOR COMMERCIAL POOL, THUS AREA |
| | LIGHTING IS REQUIRED. INDICATE POWER SOURCE FOR SUCH |
| | LIGHTING & MAKE SURE IT COMPLIES W/FBC-E ?505. |
| | 5. PROVIDE DOCUMENTATION ON ADA LIFT IF IT HAS ANY |
| | ELECTRICAL COMPONENTS. |
| | 6. PROVIDE A DETAIL OF THE EQUIPMENT ROOM; INDICATE THE |
| | REQUIRED CLEARANCES. |
| | |
| | ALL THIS CAN BE ACCOMPLISHED WITH IDENTIFYING NOTES ON |
| | THE DRAWINGS. YOU DON?T HAVE TO DRAW THE ENTIRE RISER |
| | DIAGRAM AS SHOWN ON E4.01 AS IT DOESN?T PERTAIN TO THIS |
| | PERMIT, BUT YOU DO HAVE TO INCLUDE A RISER DIAGRAM |
| | SHOWING PANEL P AS THE SOURCE OF SERVICE. INDICATE ITS |
| | LOCATION AND ADD THE NOTES INDICATED ABOVE. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO |
| | CONTACT ME. |
| | |
| | RESPECTFULLY SUBMITTED, |
| | |
| | MIKE ALBARRAN |
| | |