Plan Review Notes
Plan Review Notes For Permit 15040655
Permit Number 15040655
Review Stop P
Sequence Number 1
Notes
Date Text
2015-05-02 09:33:331) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED
 WITHIN 200 FEET WALKING DISTANCE OF THE NEAREST WATER'S
 EDGE OF EACH POOL SERVED BY THE FACILITIES. 2010 FBC
 SEC. 424.1.6.
 2) THE WATER FILL FOR THE COLLECTOR TANK SHALL BE
 EQUIPPED WITH A REDUCED PRESSURE BACKFLOW PREVENTER PER
 CITY ORDINANCE AND THE CITY'S CROSS CONNECTION CONTROL
 MANUAL.
 3) SUBMIT MANUFACTURING SPECS FOR THE POOL HEATERS. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) PROVIDE CALCULATIONS ON THE PLAN THAT THE MAXIMUM
 FILTRATION RATE THROUGH THE CARTRIDGE FILTERS DOES NOT
 EXCEED 0.075 PER THE 2010 FBC SEC.424.1.6.5.5.1.
 5) THE EQUIPMENT ROOM SHALL HAVE POSITIVE FLOOR
 DRAINAGE PER 2010 FBC SEC.424.1.5.4.
 6) SUBMIT DOCUMENTATION THAT THE GRATING ON THE POOL
 MAIN DRAIN COMPLIES WITH 2010 FBC SEC.424.1.6.5.10.2.
 SUBMIT MANUF. SPECIFICATIONS FOR THE MAIN DRAIN COVER.
 7) THE PLANS SHOW THE POOL WATER DISCHARGING TO THE
 STORM WATER SYSTEM. POOL WATER SHALL NOT DISCHARGE TO
 THE CITY'S STORMWATER SYSTEM PER CITY ORDINANCE
 SEC.90-203.
 8) SUBMIT MSDS DOCUMENTS FOR THE THE CHLORINE AND THE
 "ACID'.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 9) SUBMIT DETAILS/SPECS FOR THE CHEMICAL FEEDERS. THE
 FEEDERS SHALL COMPLY WITH ANSI/NSF 50 - 2007 PER 2010
 FBC SEC.424.1.6.5.16.
 10) THE POOL HEATERS SHALL HAVE VALVES PROVIDED WHICH
 ALLOW FOR THE ISOLATION OR REMOVAL OF THE HEATER FROM
 THE SYSTEM. THE DESIGN DOES NOT APPEAR TO MEET THIS
 REQUIREMENT. SEE 2010 FBC SEC.424.1.6.5.14.
  
 THIS REVIEW DID NOT INCLUDE THE POOL HOUSE BUILDING FOR
 THE MINIMUM SANITARY FACILITY REQUIREMENTS FOR THE
 RESTROOMS.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  