| 2015-05-02 09:33:33 | 1) THE ENTRY DOORS OF ALL RESTROOMS SHALL BE LOCATED |
| | WITHIN 200 FEET WALKING DISTANCE OF THE NEAREST WATER'S |
| | EDGE OF EACH POOL SERVED BY THE FACILITIES. 2010 FBC |
| | SEC. 424.1.6. |
| | 2) THE WATER FILL FOR THE COLLECTOR TANK SHALL BE |
| | EQUIPPED WITH A REDUCED PRESSURE BACKFLOW PREVENTER PER |
| | CITY ORDINANCE AND THE CITY'S CROSS CONNECTION CONTROL |
| | MANUAL. |
| | 3) SUBMIT MANUFACTURING SPECS FOR THE POOL HEATERS. WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 4) PROVIDE CALCULATIONS ON THE PLAN THAT THE MAXIMUM |
| | FILTRATION RATE THROUGH THE CARTRIDGE FILTERS DOES NOT |
| | EXCEED 0.075 PER THE 2010 FBC SEC.424.1.6.5.5.1. |
| | 5) THE EQUIPMENT ROOM SHALL HAVE POSITIVE FLOOR |
| | DRAINAGE PER 2010 FBC SEC.424.1.5.4. |
| | 6) SUBMIT DOCUMENTATION THAT THE GRATING ON THE POOL |
| | MAIN DRAIN COMPLIES WITH 2010 FBC SEC.424.1.6.5.10.2. |
| | SUBMIT MANUF. SPECIFICATIONS FOR THE MAIN DRAIN COVER. |
| | 7) THE PLANS SHOW THE POOL WATER DISCHARGING TO THE |
| | STORM WATER SYSTEM. POOL WATER SHALL NOT DISCHARGE TO |
| | THE CITY'S STORMWATER SYSTEM PER CITY ORDINANCE |
| | SEC.90-203. |
| | 8) SUBMIT MSDS DOCUMENTS FOR THE THE CHLORINE AND THE |
| | "ACID'.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 9) SUBMIT DETAILS/SPECS FOR THE CHEMICAL FEEDERS. THE |
| | FEEDERS SHALL COMPLY WITH ANSI/NSF 50 - 2007 PER 2010 |
| | FBC SEC.424.1.6.5.16. |
| | 10) THE POOL HEATERS SHALL HAVE VALVES PROVIDED WHICH |
| | ALLOW FOR THE ISOLATION OR REMOVAL OF THE HEATER FROM |
| | THE SYSTEM. THE DESIGN DOES NOT APPEAR TO MEET THIS |
| | REQUIREMENT. SEE 2010 FBC SEC.424.1.6.5.14. |
| | |
| | THIS REVIEW DID NOT INCLUDE THE POOL HOUSE BUILDING FOR |
| | THE MINIMUM SANITARY FACILITY REQUIREMENTS FOR THE |
| | RESTROOMS. |
| | |
| | |
| | |