| Plan Review Notes For Permit 15040655 |
| Permit Number |
15040655 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-08 16:42:02 | | | | 15040663 | | | 600 OKEECHOBEE BLVD. | | | COMMERCIAL POOL | | | | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS | | | | | | PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL | | | PANELBOARD FOR THE POOL. NEC 215.5 | | | | | | VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE | | | SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT | | | GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC | | | 250.22, 680.21, 680.25 | | | | | | SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR | | | THE NEW PANEL BOARD SERVING THE SPA EQUIPMENT. NEC | | | 110.26 | | | | | | VERIFY ALL SIGHT LIGHTING AND DECORATIVE LIGHTING IS | | | GFCI PROTECTED AND LOCATED MORE THAN 5 FEET FROM THE | | | POOL AND ABOVE 12 FEET. NEC 680.42, 680.22 (C), | | | 680.43(B) | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|