| 2015-05-08 16:46:35 | 1ST REVIEW: FBC 2010 | | | | | | 1009.3.2 SUBMERGED DEPTH. | | | SLOPED ENTRIES SHALL EXTEND TO A DEPTH OF 24 INCHES | | | (610 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM BELOW | | | THE STATIONARY WATER LEVEL. WHERE LANDINGS ARE REQUIRED | | | BY 405.7, AT LEAST ONE LANDING SHALL BE LOCATED 24 | | | INCHES (610 MM) MINIMUM AND 30 INCHES (760 MM) MAXIMUM | | | BELOW THE STATIONARY WATER LEVEL. | | | | | | REVISE SECTION BB ON SHEET 4 TO PROVIDE A LANDING | | | | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | | | | 2015-05-04 11:33:08 | | | | 15040663 | | | 600 OKEECHOBEE BLVD. | | | COMMERCIAL POOL | | | | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS | | | | | | PROVIDE FEEDER DETAILS FOR THE NEW ELECTRICAL | | | PANELBOARD FOR THE POOL. NEC 215.5 | | | | | | VERIFY THAT ALL FEEDERS FROM THE ELECTRICAL SERVICE | | | SOURCE INCLUDE A FULL SIZE INSULATED COPPER EQUIPMENT | | | GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH NEC | | | 250.22, 680.21, 680.25 | | | | | | SHOW THE LOCATION AND SAFETY CLEARANCES REQUIRED FOR | | | THE NEW PANEL BOARD SERVING THE SPA EQUIPMENT. NEC | | | 110.26 | | | | | | VERIFY ALL SIGHT LIGHTING AND DECORATIVE LIGHTING IS | | | GFCI PROTECTED AND LOCATED MORE THAN 5 FEET FROM THE | | | POOL AND ABOVE 12 FEET. NEC 680.42, 680.22 (C), | | | 680.43(B) | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS REVIEW | | | | | | |
|