Plan Review Notes
Plan Review Notes For Permit 15040645
Permit Number 15040645
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-04-21 13:46:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 1) ALL REQUIRED EXITS FROM THE EXISTING FACILITY SHALL
 BE MAINTAINED THROUGHT THE CONSTRUCTION PERIOD.
  
 2) THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
 3) SHEET G-101 SHOWS INCORRECT REFERENCES TO THE FIRE
 CODE: THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS
 OF THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE
 INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND
 ALL OTHER APPLICABLE CODES OR STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 4) SHEET G-101 SHOWS EXIT ACCESS THROUGH CORRIDOR 103
 LEADING TO THE FRONT DOOR. THERE IS NO EXIT SIGN IN
 THAT CORRIDOR. AN EXIT SIGN IS REQUIRED IN CORRIDOR 103
 DIRECTING EGRESS TO THE FRONT DOOR.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved