| Plan Review Notes For Permit 15040628 |
| Permit Number |
15040628 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-21 08:25:01 | 1) SUBMIT A ROOF PLAN SHOWING THE LOCATION AND SIZE OF | | | THE GUTTERS AND DOWNSPOUTS. WPB AMEND. TO 2010 FBC SEC. | | | 107,2,1, | | | 2) THE GUTTERS SHALL BE SIZED PER TABLE 1106.6 OF THE | | | 2010 FPC. SUBMIT CALCULATIONS, | | | 3) SUBMIT A PLAN THAT SHOWS THE SQUARE FOOTAGE OF THE | | | ROOF THAT IS DRAINED BY EACH GUTTER. WPB AMEND. TO 2010 | | | FBC SEC.107.2.1. | | | 4) THE DOWNSPOUTS SHALL BE SIZED PERR THE 2010 FBC | | | TABLE 1106.2 (1) FOR CIRCULAR VERTICAL CONDUCTORS AND | | | LEADERS AND TABLE 1106.2 (2) FOR RECTANGULAR VERTICAL | | | CONDUCTORS AND LEADERS. | | | 5) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE | | | FOOT AWAY FROM THE STRUCTURE SIDEWALL PER THE 2010 FBC | | | SEC.1503.7. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|