| 2015-05-18 17:03:24 | 5/18/2015 | | | PROJECT: | | | PERMIT#: | | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | ELECTRICAL PLAN REVIEW | | | ACTION: | | | | | | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) PROVIDE EMERGENCY LIGHTING SO THAT THE FAILURE OF | | | ANY INDIVIDUAL LIGHTING ELEMENT, SUCH AS THE BURNING | | | OUT OF A LAMP, CANNOT LEAVE IN TOTAL DARKNESS ANY SPACE | | | THAT REQUIRES EMERGENCY ILLUMINATION. NEC 700.16 | | | | | | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, | | | SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, | | | COMMUNICATION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | | REVIEW. | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|