2015-07-29 16:42:41 
 7/29/15 REVIEW FAILED
  
  
 1.RISER DIAGRAM DOES NOT SHOW DRAIN FOR VACUM TANK MUST
 DRAIN DIRECTLY INTO SANITARY THROUGH TRAP, SIZE TO
 MANNAFACTURE SPECS.
 MUST COMPLY WITH NFPA 99 5.3.3.6.3.1 AND FBCP 2010
 713.7
  
 2. RISER DIAGRAM DOES NOT SHOW PLASTER TRAP PLEASE
 CLARIFY
  
 3.WATER RISER DIAGRAM IS SIZED INNCORECTLY USE TABLE
 E201.1 FBCP 2010
  
 4.EXAUST FROM VACUM SYSTEM MUST DISTARGE ABOVE ROOF
 FBCP 713.6
  
  
  