| 2015-07-29 16:42:41 | | | | 7/29/15 REVIEW FAILED | | | | | | | | | 1.RISER DIAGRAM DOES NOT SHOW DRAIN FOR VACUM TANK MUST | | | DRAIN DIRECTLY INTO SANITARY THROUGH TRAP, SIZE TO | | | MANNAFACTURE SPECS. | | | MUST COMPLY WITH NFPA 99 5.3.3.6.3.1 AND FBCP 2010 | | | 713.7 | | | | | | 2. RISER DIAGRAM DOES NOT SHOW PLASTER TRAP PLEASE | | | CLARIFY | | | | | | 3.WATER RISER DIAGRAM IS SIZED INNCORECTLY USE TABLE | | | E201.1 FBCP 2010 | | | | | | 4.EXAUST FROM VACUM SYSTEM MUST DISTARGE ABOVE ROOF | | | FBCP 713.6 | | | | | | | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | 561-805-6711 | | | [email protected] | | | |
|