| Plan Review Notes For Permit 15040620 |
| Permit Number |
15040620 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-06 06:05:30 | 1) SUBMIT PIPING RISER DIAGRAMS FOR ALL MEDICAL GAS | | | SYSTEMS ( VACUUM & COMPRESSED AIR). THE DESIGN & | | | INSTALLATION SHALL COMPLY WITH NFPA 99C FOR A LEVEL 3 | | | PIPING SYSTEM. 2ND REQUEST. THE SUBMITTED RESPONSE OF | | | "EQUIPMENT INFORMATION PROVIDED" DDOES NOT SATISFY THE | | | PLAN REVIEW COMMENT. | | | 2) INDICATE THE USE OF THE 3/4" DRAIN LINE UNDER THE | | | SLAB. THE MINIMUM SIZE DRAIN SHALL BE 1 1/2" IN | | | ACCORDANCE WITH 2010 FPC TABLE 710.1 (2) OR YOU MAY USE | | | NFPA PPC DRAIN SIZE OPTIONS. CLARIFY. | | | 3) SUBMIT A LEGIBLE DETAIL OF THE EQUIPMENT FLOOR BOX | | | ON SHT. P-1. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 4) COMPRESSED AIR AND VACUUM PIPING SHALL COMPLY W/ | | | NFPA 99 CHAPTS. 5 & 14. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|