Plan Review Notes
Plan Review Notes For Permit 15040620
Permit Number 15040620
Review Stop P
Sequence Number 2
Notes
Date Text
2015-07-06 06:05:301) SUBMIT PIPING RISER DIAGRAMS FOR ALL MEDICAL GAS
 SYSTEMS ( VACUUM & COMPRESSED AIR). THE DESIGN &
 INSTALLATION SHALL COMPLY WITH NFPA 99C FOR A LEVEL 3
 PIPING SYSTEM. 2ND REQUEST. THE SUBMITTED RESPONSE OF
 "EQUIPMENT INFORMATION PROVIDED" DDOES NOT SATISFY THE
 PLAN REVIEW COMMENT.
 2) INDICATE THE USE OF THE 3/4" DRAIN LINE UNDER THE
 SLAB. THE MINIMUM SIZE DRAIN SHALL BE 1 1/2" IN
 ACCORDANCE WITH 2010 FPC TABLE 710.1 (2) OR YOU MAY USE
 NFPA PPC DRAIN SIZE OPTIONS. CLARIFY.
 3) SUBMIT A LEGIBLE DETAIL OF THE EQUIPMENT FLOOR BOX
 ON SHT. P-1. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) COMPRESSED AIR AND VACUUM PIPING SHALL COMPLY W/
 NFPA 99 CHAPTS. 5 & 14.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved