2015-07-08 09:02:222ND REVIEW: FBC-10 MECHANICAL
  
 1) THE REVISED PLAN SHOWS AN 8" ROUND MAIN RETURN DUCT
 AT THE RTU WHICH IS UNDERSIZED FOR A LOW OR MEDIUM
 PRESSURE SYSTEM RETURNING 1600 CFM'S OF SUPPLY AIR. IS
 THIS A TYPO?
 2) IF THE RTU IS EXISTING PLEASE LABEL IT AS SUCH.
 3) PLEASE PLACE A SYMBOL "S" ON THE PLAN TO SHOW THE
 LOCATION OF THE NEW DUCT SMOKE DETECTOR- SECTION 606.2.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER