| Plan Review Notes For Permit 15040620 |
| Permit Number |
15040620 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-07-08 13:39:29 | WITH THE EXCEPTION TO ELECTRICAL COMMENT # 7 EVERYTHING | | | HAS BEEN ADDRESSED AS REQUIRED. WITH REGARDS TO THE | | | REQUIRED ESSENTIAL ELECTRICAL SYSTEM, YOU HAVE IF I'M | | | NOT MISTAKEN ONLY INCLUDED THE EMERGENCY LIGHT ON THE | | | SYSTEM. THERE'S A BIT MORE TO WHAT COMPRISES AN | | | ESSENTIAL ELECTRICAL SYSTEM. FOR FURTHER INFORMATION ON | | | THAT CONSULT NFPA 70, 2008 EDITION SECTION 517.25 OR | | | NFPA 99, 2005 SECTION 4.4. IF YOU WISH, FEEL FREE TO | | | CONTACT ME DIRECTLY. MIKE ALBARRAN (561) 805-6746 OR | | | [email protected]. |
|