| 2015-06-21 09:35:43 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15040620 |
| | ADD: 10130 NORTHLAKE BLVD. # 118 |
| | CONT: VN CONSTRUCTION |
| | TEL: (407)928-4148 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | I |
| | 2ND REVIEW |
| | DATE: TUES. JUNE 23/ 2015 |
| | ACTION: DENIED |
| | |
| | 1-7) COMPLIED. |
| | |
| | 8) SHEET M-1 SHOWS AN EQUIPMENT SHELTERWITH DESIGN |
| | CRITERIA OTHER THAN 170 MPH WIND SPEED, EXPOSURE "C". |
| | |
| | 8A) THE PLANS DO NOT PROVIDE COMPLIANCE WITH: 2010 |
| | FBC-B 1809.4 THE MINIMUM DEPTH OF THE FOOTING BELOW THE |
| | UNDISTRUBED GROUND SURFACE SHALL BE 12 INCHES. |
| | |
| | 8B) THE PLANS WILL NEED TO SHOW STUCCO OVER 5/8 INCH |
| | PLYWOOD. THE PLANS DO NOT INDICATE THE USE OF WIRE |
| | LATH, HOW WILL THE STUCCO BE ATTACHED TO THE PLYWOOD. |
| | PLEASE NOTE IF PAPER BACKED WIRE LATH IS USED, A BOND |
| | BREAK IN ACCORDANCE WITH THE 2010 FBC-B SECTION |
| | 14104.2.1 WILL BE REQUIRED. |
| | |
| | 8C) THE PLANS DO NOT SHOW COMPLIANCE WITH 2010 FBC-B |
| | 1403.7 PROVIDE FOR INSPECTION FOR TERMITE INFESTATION, |
| | A CLEARANCE BETWEEN THE STUCCO AND GRADE, A MINIMUM OF |
| | 6 INCHES CLEARANCE. |
| | |
| | 9) THE ROOFING PRODUCT APPROVAL MIAMI-DADE NOA |
| | 14-0611.01 WAS SUBMITTED WITH PAGES 7, 8 .9 & 27 OF |
| | SUB-SYSTEMS PLEASE IDENTIFY WHICH SUB-SYSTEM WILL BE |
| | APPLIED. NOTE IF LIMITATION # 7 OR 9. LIMITATION #7 |
| | REQUIRES ENHANCED FASTENING BY A DESIGN PROFESSIONAL. |
| | |
| | 10) NO PRODUCT APPROVAL WAS SUBMITTED FOR THE EXTERIOR |
| | DOOR. 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: (31)(A) EXTERIOR DOORS. |
| | |
| | 11) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 12) THE PLANS DO NOT INDICATE ANY NATURAL VENTILATION, |
| | FBC-B 1203.4. |
| | |
| | 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |