| 2015-05-10 09:44:46 | 1) 5% OF THE EXAM ROOM SINKS SHALL COMPLY W/2010 FL. |
| | ACCESSIBILITY CODE SEC. 212.3 & 606. |
| | 2) THE PLANS NOTE THERE IS A TOTAL OF 7 SHEETS. ONLY |
| | SIX ARE IN THE SET.CLARIFY. WPB AMEND. TO 2010 FBC SEC. |
| | 107.2.1. |
| | 3) THE SINKS IN THE BREAK ROOM, LAB & STERILE ROOM |
| | SHALL COMPLY W/2010 FL. ACCESSIBILITY CODE SEC. 212.3 & |
| | 606. |
| | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS FOR THE DENTAL CHAIRS (2 |
| | COPIES). WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 5) SHT.A-1 - SHOW THE WIDTH OF THE TOILET ROOM FIXTURE |
| | WALL. A MINIMUM WIDTH OF 85 INCHES IS REQUIRED PER 2010 |
| | FAC SEC.604.3.1, 604.8.1.6, AND SEC.405.3.1 OF 2010 FL. |
| | PLBG. CODE. |
| | 6) SUBMIT PIPING DETAILS/MANUF. SPECS FOR UNDER COUNTER |
| | WATER FILTRATION SYSTEM. FPC SEC. 611.1. |
| | 7) SUBMIT MANUF. SPCIFICATIONS & INSTALLATION MANUALS |
| | FOR THE AIR COMPRESSOR AND VACUUM PUMP AND THE FLOOR |
| | BOXES FOR THE CHAIRS.. (2 COPIES). WPB AMEND. TO 2010 |
| | FBC SEC. 107.2.1. |
| | 8) SHT. P-1 -SIZE ALL SECTIONS OF THE HORIZONTAL |
| | SANITARY DRAIN LINE. COMPLY W/ CHAPTER 7 OF THE 2010 |
| | FL. PLUMBING CODE. |
| | 9) SHT. P-1 - THE SANITARY RISER SHOWS 2" DRAINAGE |
| | STACKS WITH 3" VENTS. CLARIFY. |
| | 10) CLEANOUTS ARE REQD. IN ALL STACKS PER FPC |
| | SEC.708.3.4. |
| | 11) SHOW THE SIZE & TERMINATION POINT OF THE WATER |
| | HEATER PAN DRAIN. COMPLY WITH FPC SEC.504.7.2. |
| | 12) THE WATER HEATER PAN SHALL COMPLY WITH 2010 FPC |
| | SEC.504.7.1. |
| | 13) THE SANITARY RISER DOES NOT CORRELATE WITH THE |
| | FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 14) THE DENTAL CHAIRS CANNOT BE INSTALLED AS DRAWN ON |
| | THE RISER. |
| | 15) SIZE ALL SECTIONS OF THE WATER PIPNG RISER.WPB |
| | AMEND. TO 2010 FBC SEC. 107.2.1. |
| | 16) SUBMIT RISER DIAGRAMS FOR ALL MEDICAL GAS (VACUUM & |
| | COMPRESSED AIR) . THE DESIGN & INSTALLATION SHALL |
| | COMPLY WITH NFPA 99C FOR A LEVEL 3 PIPING SYSTEM. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |