2015-05-27 16:33:561ST REVIEW: FBC 2010 MECHANICAL
  
 1) M-1: PROVIDE A VENTILATION CALCULATION PER TABLE
 403.3 FMC-10. INDICATE ON THE PLAN THE REQUIRED O/A,
 AND THE ACTUAL O/A BEING PROVIDED BY THE EXISTING RTU.
 2) M-1: PROVIDE A TOILET ROOM EXHAUST SYSTEM INCLUDING:
 A FAN EQUIPMENT SCHEDULE, TYPE AND SIZE OF EXHAUST
 DUCT, DUCT RUN, AND DUCT TERMINATION LOCATION.
 3) M-1: THE METHOD OF RETURN AIR SHOWN ON THE PLAN IS
 CONFUSING: THERE APPEARS TO BE A MAIN RETURN DUCT
 RUNNING DOWN THE CORRIDOR, HOWEVER THERE IS A DETAIL ON
 THE PLAN INDICATING A TRANSFER SYSTEM POSSIBLE FROM THE
 ROOMS TO THE CORRIDOR.
 PLEASE NOTE THAT USING THE CORRIDOR AS A MEANS OF
 RETURN AIR IS NOT PERMITTED PER SECTION 601.2 FMC-10.
 INDICATE THE TYPE AND SIZE OF ALL RETURN DUCTS ON THE
 PLAN TO CLARIFY.
 4) M-1: PLEASE REVIEW BUILDING PLAN REVIEW COMMENTS
 REGARDING THE NEW OUTDOOR EQUIPMENT SCREENING
 STRUCTURE. CLARIFY HOW THE ROOM WILL BE VENTILATED.
 5) M-1: TYPICALLY DENTAL VACUUM SYSTEMS ARE EQUIPPED
 WITH AIR/WATER SEPARATORS THAT REQUIRE DRAINAGE:
 PROVIDE A MEANS AND SUBMIT MANUFACTURER'S SPECS FOR
 BOTH THE VACUUM AND THE COMPRESSOR.
 PLEASE NOTE THAT THE VACUUM MAY REQUIRE AN EXHAUST
 SYTEM AS WELL: PROVIDE DETAILS.
  