| 2015-05-28 10:56:26 | THESE PLANS WERE REVIEWED AND SUBSEQUENTLY DENIED FOR |
| | THE FOLLOWING DEFICIENCIES WHICH SHALL BE CORRECTED AS |
| | INDICATED: |
| | 1. NEC 600.5 - MISSING THE DEDICATED SIGN OUTLET AT |
| | EACH PEDESTRIAN ENTRANCE TO THE BUSINESS. |
| | 2. NEC 210.62 - MISSING THE REQUIRED SHOW WINDOW |
| | OUTLETS. ONE FOR EVERY 12' OF SHOW WINDOW. |
| | 3. NEC 210.8 - EVERY OUTLET WITHIN 6' OF THE BASIN |
| | SHALL BE GFI PROTECTED. **1 |
| | 4. NEC 110.26(D) - PROVIDE ILLUMINATION ABOUT THE |
| | ELECTRICAL PANEL. |
| | 5. NEC 700.12(F) - EMERGENCY LIGHT SHALL BE ON THE SAME |
| | CIRCUIT AS IS THE ROOM THEY OCCUPY. |
| | 6. NEC 517.20 - DENTIST'S WORKSTATION SHALL BE |
| | CONNECTED TO A GFI CIRCUIT/OUTLET. |
| | 7. NEC 517.25 - YOU SHALL HAVE AN ESSENTIAL ELECTRICAL |
| | SYSTEM IN OPERATION. **2 |
| | 8. REVISE THE ELECTRICAL LIGHTING PLAN TO MATCH THE |
| | LEGEND. I TRIED TO REVIEW THE LIGHTING PLAN FOR |
| | COMPLIANCE, BUT WHEN ATTEMPTED TO MATCH IT TO THE |
| | SUBMITTED LEGEND I WAS NOT ABLE TO. |
| | |
| | **1 - IF THESE OUTLETS ARE ALREADY DESIGNED ON THE GFI |
| | CIRCUIT, PLACE THE CIRCUIT NUMBER ON EACH DEVICE FOR |
| | CLARIFICATION. |
| | **2 - AN ALTERNATE SOURCE OF POWER FOR EMERGENCY |
| | SERVICE IS REQUIRED. PROVIDE A DETAILED RISER DIAGRAM |
| | INDICATING THE PRESENCE OF THE ESSENTIAL POWER SOURCE. |
| | |