2015-05-28 10:56:26THESE PLANS WERE REVIEWED AND SUBSEQUENTLY DENIED FOR
 THE FOLLOWING DEFICIENCIES WHICH SHALL BE CORRECTED AS
 INDICATED:
 1. NEC 600.5 - MISSING THE DEDICATED SIGN OUTLET AT
 EACH PEDESTRIAN ENTRANCE TO THE BUSINESS.
 2. NEC 210.62 - MISSING THE REQUIRED SHOW WINDOW
 OUTLETS. ONE FOR EVERY 12' OF SHOW WINDOW.
 3. NEC 210.8 - EVERY OUTLET WITHIN 6' OF THE BASIN
 SHALL BE GFI PROTECTED. **1
 4. NEC 110.26(D) - PROVIDE ILLUMINATION ABOUT THE
 ELECTRICAL PANEL.
 5. NEC 700.12(F) - EMERGENCY LIGHT SHALL BE ON THE SAME
 CIRCUIT AS IS THE ROOM THEY OCCUPY.
 6. NEC 517.20 - DENTIST'S WORKSTATION SHALL BE
 CONNECTED TO A GFI CIRCUIT/OUTLET.
 7. NEC 517.25 - YOU SHALL HAVE AN ESSENTIAL ELECTRICAL
 SYSTEM IN OPERATION. **2
 8. REVISE THE ELECTRICAL LIGHTING PLAN TO MATCH THE
 LEGEND. I TRIED TO REVIEW THE LIGHTING PLAN FOR
 COMPLIANCE, BUT WHEN ATTEMPTED TO MATCH IT TO THE
 SUBMITTED LEGEND I WAS NOT ABLE TO.
  
 **1 - IF THESE OUTLETS ARE ALREADY DESIGNED ON THE GFI
 CIRCUIT, PLACE THE CIRCUIT NUMBER ON EACH DEVICE FOR
 CLARIFICATION.
 **2 - AN ALTERNATE SOURCE OF POWER FOR EMERGENCY
 SERVICE IS REQUIRED. PROVIDE A DETAILED RISER DIAGRAM
 INDICATING THE PRESENCE OF THE ESSENTIAL POWER SOURCE.
  