| 2015-04-21 08:02:00 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15040620 |
| | ADD: 10130 NORTHLAKE BLVD. # 118 |
| | CONT: VN CONSTRUCTION |
| | TEL: (407)928-4148 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 21/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-1/ COVER-SHEET OCCUPANCY LOAD BUSINESS, |
| | 1,336 SQ, FT. / 100= 14 OCCUPANTS NOT 13 YOU DO NOT |
| | ROLL DOWN OR PART OF A OCCUPANT. 2010 FBC-B TABLE |
| | 1004.1.1. |
| | |
| | 2) SHEET A-1/ COVER-SHEET TYPE OF CONSTRUCTION LIST |
| | PROTECTED /SPRINKLERED, DOES NOT INDICATE THE TYPE OF |
| | CONSTRUCTION, PROTECTED MEANS CONSTRUCTION ELEMENTS ARE |
| | (1) HOUR PROTECTED, NOT SPRINKLERED. 2010 FBC-B TABLE |
| | 503 & TABLE 601. |
| | |
| | 3) SHEET A-1 THE RECEPTIONIST ENTRY DOOR IS MISSING THE |
| | 18 INCHES ON THE LATCH SIDE OF THE DOOR. 2010 |
| | FBC-ACCESSIBILITY CODE 404.2.4 MANEUVERING CLEARANCES. |
| | |
| | 4) SHEET A-1. THE UNISEX RESTROOM DOES NOT GIVE A |
| | FINISHED OR ROUGH DIMENSION AGAINST THE FIXTURE WALL |
| | SHOWING COMPLIANCE WITH 2010 FBC-ACCESSIBILITY FIGURE |
| | 604.8.1.6, 604.8.1.6 & 604.3.1. |
| | |
| | 5) SHEET A-1. ROOMS MARKED OFFICE STORAGE AND STORAGE |
| | SHOW A 2'-0" WIDE DOOR IN ROOMS APPROXIMATELY 5'-6" |
| | DEEP. SEE THE 2010 FBC-ACESS. CODE 404.2.3. OPENINGS |
| | MORE THAN 24 INCHES (610 MM) DEEP SHALL PROVIDE A CLEAR |
| | OPENING OF 36 INCHES (915 MM) MINIMUM. |
| | |
| | 6) SHEET A-1. THE (2) STORAGE ROOM DOORS SWING OVER |
| | HALF OF THE REQUIRED EXIT ACCESS CORRIDOR WIDTH. 2010 |
| | FBC-B 1008.1.9.11 |
| | DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL |
| | LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED |
| | WIDTH OF AN AISLE, CORRIDOR OR PASSAGEWAY. |
| | |
| | 7) SHEET A-1 LIFE SAFETY PLAN INDICATES EXISITNG FIRE |
| | SPRINKLER LAYOUT, NOTE THERE ARE ROOMS WITHOUT |
| | SPRINKLER HEADS IN THE ROOM. 2010 FBC-B 504.2. |
| | SPRINKLER INCREASES/ AREA. |
| | |
| | 8) SHEET M-1 SHOWS AN EQUIPMENT SHELTER BUT THERE IS NO |
| | DESIGN CRITERIA OTHER THAN 170 MPH WIND SPEED. PLEASE |
| | PROVIDE EXPOSURE CATEGORY ALSO IN THE DESIGN CRITERIA. |
| | PRESSURES FOR THE MAIN WIND FORCE RESISTING SYSTEM, & |
| | PRESSURES FOR COMPONENTS AND CLADDING. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1.1 COMMERCIAL BUILDINGS: |
| | STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | DESIGN LOADS |
| | WIND REQUIREMENTS |
| | BUILDING ENVELOPE |
| | FOUNDATION |
| | WALL SYSTEMS |
| | FLOOR SYSTEMS |
| | ROOF SYSTEMS |
| | COMPONENTS & CLADDING |
| | MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM |
| | INCLUDE THE FOLLOWING: |
| | WOOD |
| | STEEL |
| | ALUMINUM |
| | CONCRETE |
| | PLASTIC |
| | GLASS |
| | MASONRY |
| | GYPSUM BOARD AND PLASTER |
| | INSULATING (MECHANICAL) |
| | ROOFING |
| | INSULATION |
| | |
| | 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |