Plan Review Notes
Plan Review Notes For Permit 15040570
Permit Number 15040570
Review Stop B
Sequence Number 1
Notes
Date Text
2015-05-04 17:39:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE THE FLOOR PLAN TO SHOW ROOM DESIGNATIONS FBC
 107.
  
 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT, NOTE EXISTING CONDITIONS (TYPE OF WINDOW) AND
 OPENING SIZE FOR BEDROOMS, FBC R310, FBC EB 604.1. THE
 CLEAR OPENING CANNOT BE REDUCED BY MORE THAN 5%.
  
 TO PROVIDE FURTHER CLARIFICATION REGARDING INFORMATION
 NEEDED FOR BEDROOM WINDOWS WHICH ARE LESS THAN 51" IN
 HEIGHT:
  
 STATE WHAT TYPE OF WINDOW IS THERE NOW IN THE BEDROOMS
 - AWNING, CASEMENT, SINGLE HUNG?
  
 STATE WHAT THE EXISTING CLEAR OPENING DIMENSIONS ARE.
 CLEAR OPENING IS THE OPENING WHICH EXISTS WHEN THE
 WINDOW IS FULLY OPEN.
  
 STATE WHAT THE PROPOSED CLEAR OPENING DIMENSIONS ARE.
 THIS CAN BE OBTAINED FROM THE MANUFACTURER.
  
 3. THE PRODUCT APPROVAL FOR THE DOOR IS ILLEGIBLE AS IT
 WAS PRINTED "PORTRAIT" ORIENTATION RATHER THAN
 "LANDSCAPE". PROVIDE A LEGIBLE PRODUCT APPROVAL.
  
 4. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER
 SHEET FOR THE DOOR. THIS INCLUDES THE APPROVAL NUMBER
 AND STATUS, FAC9N-3.
  
 5. DOCUMENTS PREPARED BY AN ENGINEER ARE TO INCLUDE A
 TITLE BLOCK, FS471.
  
 6. VALUE IS TOO LOW. THIS IS TO INCLUDE THE MARKET
 VALUE OF LABOR, MATERIALS, OVERHEAD, PROFIT,
 ENGINEERING. PROVIDE A COST BREAKDOWN, FBC 109.
  
  