| Plan Review Notes For Permit 15040565 |
| Permit Number |
15040565 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-07 12:53:01 | PASS PROVISO | | | 1) ACCESS DOOR REQUIRED FOR DUCT DETECTOR. PER SECTION | | | 603.3 INSTALLATION 2010 FBC (M) | | | 2) PROVIDE A ENGINEER DETAIL SHOWING TYPE AND SIZE | | | OF ANCHOR USED FOR CONDENSER TIE DOWN. PER SECTION | | | 301.12 WIND RESISTANCE 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|