| Plan Review Notes For Permit 15040562 |
| Permit Number |
15040562 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-05-27 09:44:24 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) SHEET M-201: PROVIDE DETAILS AND SEQUENCE OF | | | OPERATION FOR SMOKE DETECTION AND FAN SHUT DOWN FOR THE | | | NEW AND EXISTING SYSTEMS IN THE UPS ROOM. | | | 2) M-201: PLEASE CLARIFY HOW RETURN AIR IS FUNCTIONING | | | IN THE ROOM: THE PLAN IS INDICATING ONLY SUPPLY AIR | | | BEING PROVIDED. | | | 3) M-101: PROVIDE AC LOAD CALCULATIONS FOR THE NEW | | | DUCTLESS SYSTEMS IN COMPLIANCE WITH SECTION 503.2.1 | | | FBC-10 ENERGY CONSERVATION. | | | PLEASE NOTE THE NEW UNITS SIZED AT 15 TONS TOTAL EXCEED | | | THE ADDED HEAT REJECTION LOAD OF 11.2 TONS AS SHOWN IN | | | THE SCHEDULE: OVERSIZING OF SYSTEMS IS NOT PERMITTED | | | PER SECTION 503.2.2 FBC-10 ENERGY CONSERVATION. | | | 4) PROVIDE A UL TESTED AND APPROVED THROUGH-PENETRATION | | | FIRE STOPPING ASSEMBLY ON THE PLAN FOR THE PIPES | | | PENETRATING RATED WALLS AND CEILINGS. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|