Plan Review Notes
Plan Review Notes For Permit 15040562
Permit Number 15040562
Review Stop M
Sequence Number 2
Notes
Date Text
2015-05-27 09:44:241ST REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-201: PROVIDE DETAILS AND SEQUENCE OF
 OPERATION FOR SMOKE DETECTION AND FAN SHUT DOWN FOR THE
 NEW AND EXISTING SYSTEMS IN THE UPS ROOM.
 2) M-201: PLEASE CLARIFY HOW RETURN AIR IS FUNCTIONING
 IN THE ROOM: THE PLAN IS INDICATING ONLY SUPPLY AIR
 BEING PROVIDED.
 3) M-101: PROVIDE AC LOAD CALCULATIONS FOR THE NEW
 DUCTLESS SYSTEMS IN COMPLIANCE WITH SECTION 503.2.1
 FBC-10 ENERGY CONSERVATION.
 PLEASE NOTE THE NEW UNITS SIZED AT 15 TONS TOTAL EXCEED
 THE ADDED HEAT REJECTION LOAD OF 11.2 TONS AS SHOWN IN
 THE SCHEDULE: OVERSIZING OF SYSTEMS IS NOT PERMITTED
 PER SECTION 503.2.2 FBC-10 ENERGY CONSERVATION.
 4) PROVIDE A UL TESTED AND APPROVED THROUGH-PENETRATION
 FIRE STOPPING ASSEMBLY ON THE PLAN FOR THE PIPES
 PENETRATING RATED WALLS AND CEILINGS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  