Plan Review Notes
Plan Review Notes For Permit 15040562
Permit Number 15040562
Review Stop E
Sequence Number 2
Notes
Date Text
2015-06-29 13:33:496/29/2015
 PROJECT: PBC MJC FTR CENTRAL RECORDING ROOM UPGRADES
 PERMIT#: 15040562
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PROVIDE PANEL SCHEDULES FOR ALL NEW EQUIPMENT
 INSTALLED. NEC 408.4
  
 2) PROVIDE AN ACTUAL LOAD CALCULATION OR PROVIDE A
 YEARS WORTH OF DOCUMENTED USAGE FROM THE LOCAL UTILITY.
 NEC 220.87
  
 3) PROVIDE LOAD SHEDDING DESIGN THAT INDICATE HOW THE
 LOADS WILL BE DIVERSIFIED AND SEQUENCED TO PROVIDE FULL
 GENERATOR BACK UP TO NEW UPS LOAD.
  
 4) CLARIFY RISER DIAGRAM. THE 250AMP FEEDER FROM SSDP3
 IS 3, 250 KCMIL UNTILL IT REACHES THE 5TH FL AFTER THE
 JUNCTION BOX ABOVE THE NEW UPS IT IS INDICATED THAT IT
 CHANGES TO 600 KCMIL AND ONE #3 GRND. THIS APPREARS TO
 BE A MIS IDENTIFIED FEEDER AND THE 600 KCMIL WAS MEANT
 FOR THE FEEDER TO THE PDU SEC 1 AND SEC 2
  
 5) PROVIDE UL APPROVED CONDUIT PENETRATION FIRE STOP
 DETAILS FOR FLOOR TO FLOOR PENETRATIONS. NEC 300.21
  
 6) CLARIFY CONFLICTS ON THE PLANS AS TO THE SYSTEM
 PHASE AND VOLTAGE FOR THE NEW A/C EQUIPMENT TO BE
 INSTALLED. PAGE E-201 INDICATES THE NEW CU ON THE ROOF
 IS A 480V / 3PHASE 40AMP. PAGE E-301 INDICATES TO
 CHANGE OUT A 3PHASE BREAKER TO A 1PHASE BREAKER. THE
 EQUIPMENT SUBMITTALS CALL FOR 208/230/60/3PH FOR BOTH
 INDOOR AND OUTDOOR EQUIPMENT. PROVIDING ALL PANEL
 SCHEDULES WILL HELP BUT EQUIPMENT SUBMITTALS AND SYSTEM
 VOLTAGE MUST MATCH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  