| Plan Review Notes For Permit 15040562 |
| Permit Number |
15040562 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-07 14:24:57 | PLAN DENIED | | | 1) PROVIDE A DETAIL FROM THE ENGINEER SHOWING THE | | | TYPE AND SIZE ANCHOR USED TO TIE DOWN ALL | | | EQUIPMENT ON THE ROOF . PER SECTION 301.12 | | | WIND RESISTANCE. 2010 FBC (M) | | | 2) SHOW THE FIRE DAMPERS ON EXISTING DUCT | | | 28X12 AND 24X14 SECTION 607.5.1 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|