Plan Review Notes
Plan Review Notes For Permit 15040562
Permit Number 15040562
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-07 14:24:57PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER SHOWING THE
 TYPE AND SIZE ANCHOR USED TO TIE DOWN ALL
 EQUIPMENT ON THE ROOF . PER SECTION 301.12
 WIND RESISTANCE. 2010 FBC (M)
 2) SHOW THE FIRE DAMPERS ON EXISTING DUCT
 28X12 AND 24X14 SECTION 607.5.1 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER