| Plan Review Notes For Permit 15040560 |
| Permit Number |
15040560 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-29 11:13:10 | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) THE RISER DIGRAM INDICATES A 200AMP MAIN FEEDING A | | | 100AMP PANEL. PROVIDE A CIRCUIT DIRECTORY FOR THE | | | METER/MAIN COMBO PANEL. INDICATE THE OCPD FEEDING THE | | | EXISTING 100AMP PANEL. NEC 408.4, | | | 2) INDICATE TWO GROUNDING ELECTRODES. NEC 250.56 | | | 3) PROVIDE THE FEEDER SIZE AND TYPE FEEDING THE | | | EXISTING 100AMP PANEL. WPB AMENDMENTS TO FBC | | | 107.3.5.1.2 | | | 4) PROVIDE THE REQUIRED INTERSYSTEM BONDING DEVICE. | | | NEC250.94 | | | 5) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | | INTERRUPTED. NEC 110.9 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|