| Plan Review Notes For Permit 15040554 |
| Permit Number |
15040554 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2016-03-11 07:48:51 | MECHANICAL PROVISIOS: | | | PERMIT #15040554 | | | 3/11/16 | | | | | | 1) UNDERSLAB PVC EXHAUST DUCTS SHALL BE INSPECTED PRIOR | | | TO CLOSING SLAB TRENCHES. | | | 2) PROVIDE A SUBMITTAL FOR THE PVC DUCTS REVIEWED AND | | | APPROVED BY THE ENGINEER OF RECORD. | | | 3) PROVIDE A TEST AND BALANCE REPORT FOR THE SYSTEMS, | | | AND PERFORM AN EXHAUST SYSTEM TEST AT FINAL INSPECTION. | | | 4) SUBMIT A REVISED ENERGY EFFICIENCY COMPLIANCE FORM | | | IN INK (CURRENT SUBMITTAL IS IN PENCIL). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|