| Plan Review Notes For Permit 15040554 |
| Permit Number |
15040554 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-01-30 09:48:20 | 1) ONE OF THE WASHING MACHINES & DRYERS SHALL COMPLY | | | WITH 2010 FBC-ACCESSIBILITY,SEC.611.2, 611.3,611.4. | | | SHOW ON THE PLANS.3RD REQUEST | | | 2) SHT. A8.01 - "A" ELEVATION - THE GRAB BARS SHALL BE | | | MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC- | | | ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING | | | SCHEDULE ALSO.3RD REQUEST. | | | 3) DISPENSERS SHALL BE MEASURED TO THE CENTERLINE OF | | | THE DISPENSER, NOT TO THE EDGE AS SHOWN PER FAC | | | SEC.604.7.3RD REQUEST. | | | 4) BREAKROOM SINK SHALL COMPLY W/ 2010 FAC SEC.606.3. | | | 3RD REQUEST. | | | 5) FOUR TIMES THE PLAN REVIEW FEE SHALL BE IMPOSED ON | | | THE NEXT PLAN REVIEW SUBMITTAL PER F.S. 553.80 (2) (B). | | | THE ABOVE COMMENTS HAVE NOT BEEN CORRECTED IN THREE | | | REVIEWS. | | | | | | NOTE: CONTACT ME TO REVIEW THE COMMENTS SO THE PLANS | | | CAN GET CORRECTED AND APPROVED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|