2016-01-30 09:48:201) ONE OF THE WASHING MACHINES & DRYERS SHALL COMPLY
 WITH 2010 FBC-ACCESSIBILITY,SEC.611.2, 611.3,611.4.
 SHOW ON THE PLANS.3RD REQUEST
 2) SHT. A8.01 - "A" ELEVATION - THE GRAB BARS SHALL BE
 MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC-
 ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING
 SCHEDULE ALSO.3RD REQUEST.
 3) DISPENSERS SHALL BE MEASURED TO THE CENTERLINE OF
 THE DISPENSER, NOT TO THE EDGE AS SHOWN PER FAC
 SEC.604.7.3RD REQUEST.
 4) BREAKROOM SINK SHALL COMPLY W/ 2010 FAC SEC.606.3.
 3RD REQUEST.
 5) FOUR TIMES THE PLAN REVIEW FEE SHALL BE IMPOSED ON
 THE NEXT PLAN REVIEW SUBMITTAL PER F.S. 553.80 (2) (B).
 THE ABOVE COMMENTS HAVE NOT BEEN CORRECTED IN THREE
 REVIEWS.
  
 NOTE: CONTACT ME TO REVIEW THE COMMENTS SO THE PLANS
 CAN GET CORRECTED AND APPROVED.
  