2016-02-08 10:19:423RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15040554
 2/8/16
  
 1) THE PEDICURE AREA EXHAUST SYSTEM DESIGN DOES NOT
 APPEAR TO BE A "SOURCE CAPTURE SYSTEM" AS REQUIRED BY
 FOOTNOTE H. TABLE 403.3. THE PLAN IS INDICATING EXHAUST
 GRILLS AT THE CEILING LEVEL, HOWEVER THE SOURCE OF THE
 FUMES AND ODORS ARE AT FLOOR LEVEL.
 2) PROVIDE ENLARGED DETAILS OF THE UNDERSLAB DUCT.
 REFER TO SECTION 603.8 AND INDICATE THE TYPE AND GAGE
 OF DUCT MATERIAL, HOW IT WILL BE PROTECTED AND SEALED,
 THE MINIMUM SLOPE AND ACCESS TO THE DRAINAGE POINT.
 PROVIDE A SUBMITTAL REVIEWED AND APPROVED BY THE EOR.
 3) PROVIDE ENLARGED DETAILS OF THE EXHAUST RISERS AT
 THE MANICURE TABLES- SHOW THE TYPE AND GAGE OF DUCT
 MATERIAL, HOW CONNECTIONS TO THE UNDERSLAB DUCT AND
 TABLE TOP WILL BE MADE.
 4) PLEASE PROVIDE NOTE TO CLARIFY THE SEQUENCE OF
 OPERATION FOR THE NAIL EXHAUST SYSTEMS. ARE THESE
 SYSTEMS DESIGNED TO RUN CONTINUOUSLY? ARE THE EXHAUST
 FANS LINKED WITH THE AC SYSTEMS WHICH ARE PROVIDING THE
 MAKE-UP AIR FOR THE SYSTEMS?
 5) THE AC COOLING AND HEATING CALCULATIONS ARE
 INDICATING APPROXIMARELY 10-TONS OF COOLING FOR THE
 NAIL AREA AND THE FRONT RETAIL, BREAKROOM, TOILET ROOMS
 AND AREAS ETC, HOWEVER THE TWO SYSTEMS SELECTED PROVIDE
 A TOTAL OF 11.5- TONS OF COOLING FOR THOSE AREAS.
 SENSIBLE COOLING LOAD INDICATED IN THE CALCS IS 62239
 BTUH, HOWEVER TOTAL SENSIBLE LOAD OF THE UNITS COMBINED
 IS APPROX. 83,000 BTUH- SEE SECTION 503.2.2 FBC-10
 ENERGY CONSERVATION.
 6) PLEASE CORRECT THE NOTE INDICATING FIRE DAMPERS FOR
 THE DRYER EXHAUST DUCTS- THEY ARE PROHIBITED PER
 SECTION 504.2 FBC-10 MECHANICAL.
 7) PROVIDE THE MIAMI-DADE NOA'S OR FLORIDA PRODUCT
 APPROVALS FOR EF-2, EF-3, AND THE AIR INTAKE LOUVERS.
 VERFIY ALL REQUIRED CLEARANCES AS REQUIRED BY 401.4,
 AND 501.2.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  