| Plan Review Notes For Permit 15040554 |
| Permit Number |
15040554 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2015-10-26 16:13:57 | | | | 1ST REVIEW: FBC 2014 | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: 2ND REQUEST | | | | | | 1. SHOW ON PLANS ONE OF THE WASHIN MACHINES & DRYERS | | | SHALL COMPLY WITH 2010 FBC-ACCESSIBILITY,SEC.61 1.2, | | | 611.3,611.4. | | | 2. SHT. A8. 0L - ''A" ELEVATION - THE GRAB BARS SHALL | | | BE MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC? | | | ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING | | | SCHEDULE ALSO. | | | 3. SHOW ON PLANS DISPENSERS SHALL BE MEASURED TO THE | | | CENTERLINE OF THE DISPENSER, NOT TO THE EDGE AS SHOWN | | | PER FAC SEC.604.7. | | | 4. SHOW ON PLANS BREAKROOM SINK SHALL COMPLY W/ 2010 | | | FAC SEC.606.3. | | | 5. SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL (2 COPIES) FOR THE PEDICURE CHAIRS. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. | | | 6. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINT | | | TRAP . WPB AMEND. TO 2010 FBC SEC. 107.2.1 . | | | 7. SHT. P-5 - SHOWS THE P & T LINE TO THE EXTERIOR. THE | | | P & T LINE SHALL DISCHARGE TO AN AIR GAP LOCATED IN THE | | | SAME ROOM AS THE WATER HEATER.2010 FPC SEC.504.6 (2). | | | | | | | | | | | | |
|