| Plan Review Notes For Permit 15040554 |
| Permit Number |
15040554 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-18 08:17:15 | 1) SHT. A 2.01 - CLEARLY SHOW THE WIDTH OF THE TOILET | | | ROOMS. A MINIMUM OF 85 INCHES IS REQUIRED. 2010 | | | FBC-ACCESSIBILITY, SEC.604.3.1, 606.2. | | | 2) ONE OF THE WASHING MACHINES & DRYERS SHALL COMPLY | | | WITH 2010 FBC-ACCESSIBILITY,SEC.611.2, 611.3,611.4. | | | 3) SHT. A8.01 - "A" ELEVATION - THE GRAB BARS SHALL BE | | | MEASURED TO THE TOP OF THE GRIPPING SURFACE.FBC- | | | ACCESSIBILITY, SEC. 609.4. REFER TO ACCESSORY MOUNTING | | | SCHEDULE ALSO. | | | 4) DISPENSERS SHALL BE MEASURED TO THE CENTERLINE OF | | | THE DISPENSER, NOT TO THE EDGE AS SHOWN PER FAC | | | SEC.604.7. | | | 5) BREAKROOM SINK SHALL COMPLY W/ 2010 FAC SEC.606.3. | | | 6) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION | | | MANUAL (2 COPIES) FOR THE PEDICURE CHAIRS. WPB AMEND. | | | TO 2010 FBC SEC. 107.2.1. | | | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE LINT | | | TRAP. WPB AMEND. TO 2010 FBC SEC. 107.2.1. | | | 8) SHT. P-5 - SHOWS THE P & T LINE TO THE EXTERIOR. THE | | | P & T LINE SHALL DISCHARGE TO AN AIR GAP LOCATED IN THE | | | SAME ROOM AS THE WATER HEATER.2010 FPC SEC.504.6 (2). | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|