| Plan Review Notes For Permit 15040554 |
| Permit Number |
15040554 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-29 17:23:00 | 1ST REVIEW: FBC 2010 MECHANICAL | | | | | | 1) SHEET M1: PER NOTES 6 & 7 ON THE PLAN, SHOW THE | | | MOTORIZED DAMPER FOR EF2. | | | 2) M2: GENERAL NOTE #12 INDICATES THAT CO2 SENSORS WILL | | | MONITOR THE QUALITY OF AIR IN THE SPACE, HOWEVER NO | | | SENSORS ARE SHOWN ON THE PLANS. | | | PLEASE CLARIFY HOW THIS SYSTEM DESIGN IS MEETING THE | | | INTENT OF TABLE 403.3 FMC-10, AND TABLE 6-4 ASHRAE 62.1 | | | WHICH REQUIRES CAPTURING THE CHEMICAL FUMES AT THEIR | | | SOURCES AND EXHAUSTING THEM FROM THE SPACE. | | | THE DESIGN DOES NOT INDICATE ANY EXHAUST HOODS OR DUCTS | | | AT THE STATIONS. IN ADDITION, PLEASE CLARIFY IF THE CO2 | | | SENSORS WILL ACTIVATE THE SYSTEM UPON DETECTION OF | | | CHEMICAL FUMES. | | | 3) PROVIDE TWO COPIES OF MIAMI-DADE NOA'S OR FL. | | | PRODUCT APPROVALS FOR THE AC STAND, AND THE INTAKE AND | | | EXHAUST LOUVERS. | | | 4) PROVIDE MANUFACTURER'S SPECIFICATIONS (CUT SHEET) | | | FOR THE EXHAUST FAN. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|