Plan Review Notes
Plan Review Notes For Permit 15040554
Permit Number 15040554
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2015-04-17 10:55:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A2.00 INDICATES AN EXIT EGRESS LAYOUT THAT IS
 NOT APPROVED. THESE EXITS ARE NOT REMOTELY LOCATED. THE
 SEPARATION DISTANCE DOES NOT MEET THE REQUIREMENTS OF
 NFPA 101, CHAPTER 7, 7.5.1.3.3. THE SEPARATION DISTANCE
 SHALL BE 1/3 OF THE DIAGONAL MEASURED IN A STRAIGHT
 LINE BETWEEN THE NEAREST EDGE OF THE EXITS, EXIT
 ACCESS, OR EXIT DISCHAGES. AN ADDITIONAL EXIT IS
 REQUIRED THAT IS REMOTELY LOCATED AND MEETING THE
 DISTANCE REQUIRMENT.
  
 2) SHEET A0.01 INDICATES AN INCORRECT FIRE CODE
 REFERENCE. THE PROPOSED PROJECT SHALL MEET THE
 REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE
 PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1
 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR
 STANDARDS.
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 3) SHEET A2.00 THE NATURE OF THE REMODEL REQUIRES AN
 EVALUATION OF THE FIRE ALARM AND SPRINKLER SYSTEM FOR
 CODE COVERAGE AND COMPLIANCE.
 PROVIDE A NOTE STATING: THE LIFE SAFETY SYSTEMS, FIRE
 ALARM AND/OR FIRE SPRINKLER SHALL REMAIN ACTIVE
 THROUGHOUT THE CONSTRUCTION PERIOD.
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  


Account Summary | Usage Policy | Privacy Policy