Plan Review Notes
Plan Review Notes For Permit 15040554
Permit Number 15040554
Review Stop E
Sequence Number 1
Notes
Date Text
2015-05-18 14:02:375/18/2015
 PROJECT: NAIL SALON
 PERMIT#: 15040554
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) REVISE THE LIGHTING PLAN AND THE PANEL SCHEDULE TO
 INCLUDE THE EMERGENCY/EXIT LIGHT CIRCUIT IS THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN
 THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC
 700.12.
  
 2) REVISE THE FLOOR PLAN AND THE PANEL SCHEDULE FOR THE
 WATER HEATER CIRCUIT. IT APPEARS TO BE A TYPO BUT THE
 CIRCUIT IS IDENTIFIED AS A 3POLE CIRCUIT BUT HAS ONE
 POLE IDENTIFIED AS 50AMP AND THE OTHER TWO AS 30AMP.
 PLEASE CLARIFY.
  
 3) INDICATE OR VERIFY THE REQUIRED GFI RECEPTACLE ON
 THE ROOF WITHIN SIGHT OF THE MECHANICAL EQUIPMENT. NEC
 210.63 SEE 210.8(A)(3),
  
 4) PROVIDE SUBMITTALS ON EQUIPMENT SUCH AS PEDICURE
 CHAIRS, NAIL DRYERS,
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  