| 2015-05-18 14:02:37 | 5/18/2015 |
| | PROJECT: NAIL SALON |
| | PERMIT#: 15040554 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW |
| | COMMENTS: |
| | |
| | 1) REVISE THE LIGHTING PLAN AND THE PANEL SCHEDULE TO |
| | INCLUDE THE EMERGENCY/EXIT LIGHT CIRCUIT IS THE SAME |
| | BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN |
| | THE AREA AND CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC |
| | 700.12. |
| | |
| | 2) REVISE THE FLOOR PLAN AND THE PANEL SCHEDULE FOR THE |
| | WATER HEATER CIRCUIT. IT APPEARS TO BE A TYPO BUT THE |
| | CIRCUIT IS IDENTIFIED AS A 3POLE CIRCUIT BUT HAS ONE |
| | POLE IDENTIFIED AS 50AMP AND THE OTHER TWO AS 30AMP. |
| | PLEASE CLARIFY. |
| | |
| | 3) INDICATE OR VERIFY THE REQUIRED GFI RECEPTACLE ON |
| | THE ROOF WITHIN SIGHT OF THE MECHANICAL EQUIPMENT. NEC |
| | 210.63 SEE 210.8(A)(3), |
| | |
| | 4) PROVIDE SUBMITTALS ON EQUIPMENT SUCH AS PEDICURE |
| | CHAIRS, NAIL DRYERS, |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |