| Plan Review Notes For Permit 15040527 |
| Permit Number |
15040527 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-15 13:13:22 | APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED | | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION | | | FEE(S). | | | | | | THE PLAN IS CALLING FOR THE REMOVAL OF AN OUTLET IN ONE | | | BATHROOM. SEE THE CODE ARTICLE BELOW THAT STATES A GFI | | | OUTLETS IS REQUIRED WITHIN 3FT OF A RESIDENTIAL | | | BATHROOM SINK. | | | THEREFORE PROVIDE A GFI RECEPTACLE WITHIN 3FT OF EACH | | | OF THE BATHROOM SINKS. | | | | | | 1) NEC 210.52 (D) BATHROOMS. IN DWELLING UNITS, AT | | | LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED IN | | | BATHROOMS WITHIN (3 FT) OF THE OUTSIDE EDGE OF EACH | | | BASIN. THE RECEPTACLE OUTLET SHALL BE LOCATED ON A WALL | | | OR PARTITION THAT IS ADJACENT TO THE BASIN OR BASIN | | | COUNTERTOP, OR INSTALLED ON THE SIDE OR FACE OF THE | | | BASIN CABINET NOT MORE THAN (12 IN.) BELOW THE | | | COUNTERTOP. ACCORDING TO THE CONTRACTOR. THERE IS AN | | | EXISTING OUTLET WITHIN THE 3' SPACE NEEDED TO COMPLY | | | WITH THIS CODE. NEC 210.52(D) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | | | | |
|