| Plan Review Notes For Permit 15040519 |
| Permit Number |
15040519 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-15 13:13:33 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SOUND INSULATION: PROVIDE TWO COPIES OF ASTM E84 OR | | | UL 723 TEST SHOWING COMPLIANCE WITH THE FLAME SPREAD | | | INDEX AND SMOKE-DEVELOPED INDEX AS REQUIRED BY SEC. . | | | 719.1 OF 2010 FBC-BUILDING. | | | | | | 2- SOUND INSULATION: PROVIDE TWO COPIES OF ASTM E 90 | | | TEST SHOWING COMPLIANCE WITH THE SOUND TRANSMISSION | | | CLASS (STC) AS REQUIRED BY SEC. 1207.2 OF 2010 | | | FBC-BUILDING. | | | | | | 3- SOUND INSULATION: PROVIDE TWO COPIES OF ASTM E 492 | | | TEST SHOWING COMPLIANCE WITH THE IMPACT INSULATION | | | CLASS (IIC) AS REQUIRED BY SEC. 1207.3 OF 2010 | | | FBC-BUILDING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT. | | | (561)805-6712 | | | [email protected] |
|