Plan Review Notes
Plan Review Notes For Permit 15040517
Permit Number 15040517
Review Stop E
Sequence Number 2
Notes
Date Text
2015-05-07 09:59:155/7/2015
 PROJECT: AVALON NAIL AND SPA
 PERMIT#: 14081190
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW FOR REVISION #15040517
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) FBC-E 502.3.8 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING
 ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE
 DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF
 AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING
 CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A
 GASKET OR CAULK BETWEEN THE HOUSING AND INTERIOR WALL
 OR CEILING COVERING.
  
 2) 410.6 LISTING REQUIRED. ALL LUMINAIRES AND
 LAMPHOLDERS SHALL BE LISTED.
  
 3) THIS ELECTRICAL DESIGN SUBMITTED IS APPROVED FOR
 PERMIT.
 THE FIRE ALARM SYSTEM MODIFICATION HAS NOT BEEN
 REVIEWED OR APPROVED FOR PERMIT AT THIS TIME. PLEASE
 PROVIDE A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 FOR THE FIRE ALARM SCOPE OF WORK AS WELL AS ANY LOW
 VOLTAGE SPECIALTY SYSTEMS SUCH AS BUT NOT LIMITED TO
 THE FOLLOWING: FIRE ALARM, SITE LIGHTING, GENERATORS.
 DATA/COMMUNICATION, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, AND/OR AUDIO/VIDEO IF PROPOSED FOR FUTURE USE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  