| 2015-05-07 09:59:15 | 5/7/2015 |
| | PROJECT: AVALON NAIL AND SPA |
| | PERMIT#: 14081190 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW FOR REVISION #15040517 |
| | ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN |
| | APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED |
| | DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | |
| | 1) FBC-E 502.3.8 RECESSED LIGHTING. |
| | RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL |
| | ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN |
| | CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED |
| | LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING |
| | ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE |
| | DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF |
| | AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING |
| | CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A |
| | GASKET OR CAULK BETWEEN THE HOUSING AND INTERIOR WALL |
| | OR CEILING COVERING. |
| | |
| | 2) 410.6 LISTING REQUIRED. ALL LUMINAIRES AND |
| | LAMPHOLDERS SHALL BE LISTED. |
| | |
| | 3) THIS ELECTRICAL DESIGN SUBMITTED IS APPROVED FOR |
| | PERMIT. |
| | THE FIRE ALARM SYSTEM MODIFICATION HAS NOT BEEN |
| | REVIEWED OR APPROVED FOR PERMIT AT THIS TIME. PLEASE |
| | PROVIDE A SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | FOR THE FIRE ALARM SCOPE OF WORK AS WELL AS ANY LOW |
| | VOLTAGE SPECIALTY SYSTEMS SUCH AS BUT NOT LIMITED TO |
| | THE FOLLOWING: FIRE ALARM, SITE LIGHTING, GENERATORS. |
| | DATA/COMMUNICATION, ACCESS CONTROL SYSTEM, SECURITY, |
| | CCTV, AND/OR AUDIO/VIDEO IF PROPOSED FOR FUTURE USE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |