| Plan Review Notes For Permit 15040517 |
| Permit Number |
15040517 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-20 14:20:43 | REVISE PLANS IN RESPONSE TO THE FOLLOWING REVIEW | | | COMMENTS: | | | | | | 1) THE RISER DIAGRAM INDICATES AN EXISTING 200AMP | | | 480VOLT FUSABLE MAIN FEEDING A 100AMP MAIN CIRCUIT | | | BREAKER PANEL WITH A 1/0 3PHASE FEEDER. | | | THE ISSUE HERE IS THE SIZE OF THE FUSES IN THE EXISTING | | | FUSABLE MAIN. THE PLAN NEEDS TO INDICATE THE FUSES | | | REDUCED IN SIZE TO BE COMPATIBLE WITH THE SIZE OF THE | | | FEEDER. IF IT IS THE INTENT OF THE DESIGNER TO USE A | | | 1/0 3 PHASE FEEDER THE FUSES CAN NOT EXCEED 150AMPS. | | | NEC 240.4 | | | | | | 2) PROVIDE MANUFACTURER SUBMITTALS FOR PEDICURE CHAR | | | ELECTRICAL REQUIREMENTS.ALL INDICATIONS ARE THAT ALL | | | BRANCH CIRCUIT WIRIG AND DEVICES SHALL BE A MINIMUM OF | | | 20AMPS EXCEPT FOR NOTE #6 UNDER THE HEADING | | | "RECEPTACLES AND SWITCHES" SHEET E-1. WPB AMENDMENTS TO | | | THE FBC 107.3.2 | | | | | | 3) INDICATE THE REQUIRED GFI RECEPTACLE WITHIN SIGHT OF | | | THE MECHANICCAL EQUIPMENT. NEC 210.63 | | | | | | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY | | | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS | | | ARE REQUIRED FOR FIRE ALARM, ACCESS CONTROL SYSTEM, | | | SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, | | | COMMUNICATION. | | | | | | | | | |
|