| Plan Review Notes For Permit 15040503 |
| Permit Number |
15040503 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-05-18 07:32:46 | 5/18/15 MECHANICAL REVIEW | | | PROVISO: REMOVE BATH EXHAUST FANS AND EXHAUST DUCTS. | | | CAP AND SEAL ALL EXTERIOR OPENINGS. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | 2015-05-13 15:38:23 | REVIEW BY CHRIS COLE | | | | | | 1) SHEET D-1: PROVIDE A SCOPE OF WORK FOR MECHANICAL | | | DEMOLITION ON THE PLAN, INCLUDING REMOVAL OF ANY | | | EXHAUST FANS, DUCTS, ETC. | | | 2) PROVIDE VENTILATION AND AC LOAD CALCULATIONS FOR THE | | | PROPOSED NEW TENANT SPACE, OR PLACE A NOTE TO BE DONE | | | UNDER BUILD-OUT PERMIT. | | | | | | CHRISTOPHER COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|