2015-08-14 16:57:25RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 NOTE:
 AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 1006 OF 2010
 FBC-EXISTING BUILDING. NOTE: PLEASE COORDINATE ENERGY
 CALCULATIONS WITH PLANS AND PRODUCT APPROVALS TO AVOID
 CONFLICTS AND/OR UN-NECESSARY DELAYS.
  
 RESPONSE:
 WRONG ENERGY CALCULATIONS FORM WAS SUBMITTED. FORM
 502-2010 SUBMITTED IS FOR COMMERCIAL BUILDINGS. PROVIDE
 CORRECT FORM SEE SEC. 103.2.1.1 OF 2010 FBC-ENERGY
 CONSERVATION. PLEASE MAKE SURE ALL THE INFORMATION IS
 COMPLETED AND FORM IS SIGNED BY ALL REQUIRED PARTIES.
 ARCHITECT LISTED ON THE FORM TO SIGN AND SEAL THE
 DOCUMENT AS REQUIRED BY CHAPTER 481 FLORIDA STATUTE.
  
 2- PROVIDE COMPLETE DESIGN INFORMATION: BUILDING
 EXPOSURE, ULTIMATE AND NOMINAL WIND SPEED. SEC.
 R301.2.1.3 AND SEC. R301.2.1.4 OF 2010 FBC-RESIDENTIAL.
  
 RESPONSE:
 THIS BUILDING IS NO LOCATED IN EXPOSURE "B". REVISE AS
 REQUIRED. IT LOOKS MORE LIKE EXPOSURE "D". SEE SEC.
 R301.2.1.4 AND EXPOSURE "D" ON SEC. R301.2.1.4.3.
 REVISE AS REQUIRED OR PROVIDE COMPLETE RATIONAL
 ANALYSIS CALCULATIONS AS SPECIFIED ON THE EXCEPTION OF
 SEC. R301.2.1.4.
 AND REVISE ALL THE BUILDING AND COMPONENTS AND CLADDING
 DESIGN PRESSURES ACCORDINGLY.
  
 3- PROPERTY IS LOCATED IN FLOOD ZONE A5. CITY FLOOD
 PREVENTION AND CONTROL SEC. 94-541 REQUIRES FINISH
 FLOOR ELEVATION TO BE 6" ABOVE THE BASE FLOOR
 ELEVATION. THE BASE FLOOD ELEVATION FOR FLOOD ZONE A5
 IS 7'-0". PROVIDE COMPLETE INFORMATION SHOWING
 COMPLIANCE WITH THE FLOOD RESISTANT CONSTRUCTION AS
 REQUIRED BY SEC. R322 OF 2010 FBC-RESIDENTIAL. PROVIDE
 SURVEY SHOWING THE FINISH FLOOR ELEVATION OF EXISTING
 HOUSE AND GARAGE AND THE PROPOSED ADDITION.
  
 RESPONSE:
 (A) REVISE SURVEY SUBMITTED. THIS PROPERTY IS LOCATED
 IN FLOOD ZONE "A" NOT "B".
  
 (B) SURVEY SUBMITTED DOESN'T SPECIFY THE FINISHED FLOOR
 OF THE PROPOSED ADDITION.
  
 (C) INFORMATION SHOWN ON SURVEY AND ARCHITECTURAL PLANS
 DON'T MATCH. SURVEY CALLS FOR FINISH FLOOR ELEVATION OF
 8.4 FOR ENTIRE HOUSE AND 6.3 FOR THE GARAGE.
 ARCHITECTURAL PLANS CALLS FOR 7.9 AT FAMILY ROOM AREA
 AND THE PROPOSED ADDITION. INFORMATION NEED TO MATCH.
 SURVEY NEEDS TO BE CLEAR ON ALL FINISHED FLOOR
 ELEVATIONS. THIS INFORMATION WILL BE REQUIRED FOR THE
 ELEVATION CERTIFICATES DURING CONSTRUCTION. CORRECT ALL
 THE INFORMATION AS REQUIRED TO MATCH.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL WINDOW TYPES SHOWN ON PLANS.
 RESPONSE:
 NOT INFORMATION SUBMITTED.
  
 B) FLAT ROOF. AND CLEARLY IDENTIFY SELECTED ASSEMBLY.
 PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF THE
 SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES
 REQUIRED BY SEC. R301 OF 2010 FBC-RESIDENTIAL.
 RESPONSE:
 ARCHITECT SPECIFIED NOA ON SHEET A-1.1. NEED TO SUBMIT
 NOA. IDENTIFY APPROVED ASSEMBLY AND NEED THE SIGNED AND
 SEALED RAS 117 CALCULATIONS.
  
 C) HUGHES, SEMCO AND SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED ON ALL DETAILS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND THE PAGE SHOWING THE
 SPECIFIED CONNECTOR. OR, LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO EACH SPECIFIED CONNECTOR.
 RESPONSE:
 UNABLE TO FIND THE MIAMI-DADE NOA'S LISTED ON THE
 DETAILS. ALSO, HUGHES TP6X SPECIFIED ON DETAIL #4 OF
 SHEET A-1.1 DOESN'T HAVE ANY NOA NUMBER.
  
 D) HARDIEBOARD FASCIA, SOFFIT AND SIDING SPECIFIED ON
 PLANS.
 RESPONSE:
 NO INFORMATION SUBMITTED. ARCHITECT SPECIFIED NOA'S ON
 DRAWINGS BUT NO INFORMATION WAS SUBMITTED.
  
 E) NEW INSWING DOOR SHOWN IN THE HOME OFFICE.
 RESPONSE:
 NO INFORMATION WAS SUBMITTED.
  
 5- DESIGN PROFESSIONAL TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 6- SHEET A-1.0: SPECIFY TYPE AND SIZE OF BEDROOM #1
 WINDOW TO VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. 604 OF 2010 FBC-EXISTING BUILDING.
 NOTE: THERE WERE SOME WINDOWS ON BEDROOM #1 THAT WERE
 ELIMINATED. EGRESS OPENINGS WERE REDUCED. NOW, THIS
 WINDOW IS THE ONLY MEANS OF EGRESS FOR THIS BEDROOM.
 NEED COMPLIANCE WITH SEC. R310 OF 2010 FBC-RESIDENTIAL.
  
 RESPONSE:
 SPECIFY SIZE AND TYPE OF EXISTING WINDOW ON PLANS.
  
 7- PROVIDE ICC CURRENT EVALUATION REPORT FOR THE
 ICYNENE INSULATION SPECIFIED ON THE WALL SECTION ON
 SHEET A-1.1. SEC. R316 2010 FBC-RESIDENTIAL AND SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 IMPORTANT: PROPERTY IS LOCATED IN FLOOD ZONE A5:
 ELEVATION CERTIFICATES WILL BE REQUIRED DURING
 CONSTRUCTION.
  
 *** PLEASE PROVIDE A RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 *** PLEASE REPLACE AND REMOVE ANY REVISED DRAWING.
 SUBMIT A COPY OF ORIGINAL DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]