Plan Review Notes
Plan Review Notes For Permit 15040499
Permit Number 15040499
Review Stop M
Sequence Number 1
Notes
Date Text
2015-05-15 07:43:59 
 1ST REVIEW: FBC 2010 MECHANICAL
 CHRISTOPHER COLE
  
 1) PROVIDE AC LOAD CALCULATIONS FOR THE NEW GAME
 ROOM/HOME OFFICE ADDTIIONS- SECTION 403.6.1 FBC-10
 ENERGY CONSERVATION.
 2) PROVIDE ENERGY CALCULATIONS PER SECTION 101.4.3
 FBC-10 ENERGY CONSERVATION. SUBMIT TWO COPIES OF EITHER
 FORM 402, OR ENERGY GAUGE FORM 405.
 3) SHEET A-3.0: A MEANS OF RETURN AIR MUST BE PROVIDED
 FROM THE NEW ADDITION ROOMS- SECTION M1602.4 FBC-10
 RESIDENTIAL.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER