| 2015-06-01 17:37:21 | THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS |
| | RESUBMITTED FOR A SECOND REVIEW: |
| | |
| | THESE PLANS WERE REVIEWED FOR COMPLIANCE WITH THE 2008 |
| | EDITION OF THE NEC, THE 2013 EDITION OF THE NFPA72, THE |
| | APPLICABLE CHAPTERS OF THE 2010 EDITION OF THE FLORIDA |
| | BUILDING CODE, FLORIDA BUILDING CODE RESIDENTIAL AND |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION. |
| | 1. KITCHEN OUTLETS AS INDICATED ON DRAWINGS DO NOT MEET |
| | MINIMUM CODE SPACING REQUIREMENTS. NEC 210.52(C) |
| | 2. IN THE OFFICE AND GAME ROOM THE RECEPTACLES SHALL BE |
| | SPACES AS I9NDICATED IN NEC 210.52(A) |
| | 3. THE A/C IN THE ATTIC REQUIRES A PERMANENT LADDER BE |
| | INSTALLED PER NEC 110.33(B) |
| | 4. AN OUTLET IS REQUIRED ON THE AREA OF THE TERRACE PER |
| | NEC 210.52(E) |
| | 5. ALL NEWLY INSTALLED RECEPTACLES SHALL BE |
| | TAMPER-RESISTANT PER NEC 406.11 |
| | 6. ALL NEW CIRCUITS SHALL BE PROTECTED W/ARC-FAULT |
| | BREAKERS AS PER NEC 210.12 |
| | 7. IF NOT ALREADY IN COMPLIANCE, YOU SHALL INSTALL |
| | SMOKE DETECTORS TO COMPLY W/FBC-R 314 & 315 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS |
| | |