2015-04-30 18:41:28****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. APPLICATION IS NOT CONSISTENT WITH THE PLANS
 SUBMITTED. APPLICATION IS FOR SHUTTERS, BUT THE PLAN IS
 FOR WINDOWS AND OTHER RELATED WORK, FBC 107.
  
 2. 1" ANCHOR SPACING PROPOSED. THIS IS NOT ALLOWED PER
 THE PRODUCT APPROVAL; MINIMUM SPACING IS 3", SEE SHEET
 11.
  
 3. VALUE TO INCLUDE LABOR, MATERIALS, OVERHEAD AND
 PROFIT, FBC 109. PROVIDE A COST BREAKDOWN FOR THIS JOB.
  
  
  