| Plan Review Notes For Permit 15040468 |
| Permit Number |
15040468 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-30 18:41:28 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. APPLICATION IS NOT CONSISTENT WITH THE PLANS | | | SUBMITTED. APPLICATION IS FOR SHUTTERS, BUT THE PLAN IS | | | FOR WINDOWS AND OTHER RELATED WORK, FBC 107. | | | | | | 2. 1" ANCHOR SPACING PROPOSED. THIS IS NOT ALLOWED PER | | | THE PRODUCT APPROVAL; MINIMUM SPACING IS 3", SEE SHEET | | | 11. | | | | | | 3. VALUE TO INCLUDE LABOR, MATERIALS, OVERHEAD AND | | | PROFIT, FBC 109. PROVIDE A COST BREAKDOWN FOR THIS JOB. | | | | | | | | | |
|