| Plan Review Notes For Permit 15040433 |
| Permit Number |
15040433 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2015-04-15 10:05:20 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR THE | | | PLUMBING WORK TO BE DONE. SHOW ORIGINATION AND | | | TERMINATION POINTS OF ALL PIPING AND PIPE SIZES. WPB | | | AMEND. TO 2010 FBC SEC. 107.3.5.1.3. | | | 2) THE DOCUMENT SUBMITTED FROM LIBERTY PUMPS IS LACKING | | | INFORMATION REQUIRED BY THE PLUMBING CODE. REFER TO THE | | | 2010 FL. PLUMBING CODE SECS.712.3.2 FOR THE MINIMUM | | | SIZE OF THE SUMP PIT. | | | 3) THE SUMP PIT SHALL BE VENTED PER FPC SEC.712.3.2 AND | | | CHAPTER 9. | | | 4) THE EJECTOR PIPING SHALL CONNECT TO THE DRAINAGE | | | SYSYTEM IN ACCORDANCE WITH THE 2010 FPC SEC. 712.3.5. | | | 5) THE MINIMUM CAPACITY OF THE PUMP SHALL COMPLY WITH | | | TABLE 712.4.2. | | | 6) SUBMIT MANUF. SPECIFICXATIONS FOR THE PUMP. | | | 7) DRINKING FOUNTAINS SHALL COMPLY WITH FL. | | | ACCESSIBILITY CODE SECS. 305 & 602.2 FOR CLEAR FLOOR | | | SPACE REQS. | | | 8) THE PLACEMENT OF THE DRINKING FOUNTAIN SHALL NOT | | | INTERFERE WITH THE APPROACH TO THE DOOR FROM THE | | | EXTERIOR FOR HANDICAP ACCESSIBILTY MANEUVERING | | | CLEARANCES.. A MINIMUM OF 18 INCHES CLEARANCE SHALL BE | | | PROVIDED ADJACENT TO THE LATCH SIDE OF THE DOOR. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|